PRODUCT DESIGN |
|
|
| ||||
HKR ELECTRICAL DATA |
|
|
|
| |||
|
|
|
|
|
|
| |
| Circuit #1 | Circuit #2 |
|
| |||
| Minimum Circuit | Maximum | Minimum Circuit | Maximum | Actual | ||
Model and Heat Kit Usage | Overcurrent | Overcurrent | kW & BTU | ||||
Ampacity | Ampacity | ||||||
| Protection (amps) | Protection (amps) | at 240V | ||||
| at 208 / 240V | at 208 / 240V | |||||
| at 208 / 240V | at 208 / 240V |
|
| |||
|
|
|
|
| |||
GPC1524M41* |
|
|
|
|
|
| |
HKR05A,CA | 24 / 27 | 30 / 30 | 4.75 / 16,200 | ||||
HKR08A,CA | 33 / 28 | 40 / 40 | 7.00 / 23,800 | ||||
HKR10A,CA | 45 / 51 | 60 / 60 | 9.50 / 32,400 | ||||
GPC1530M41* |
|
|
|
|
|
| |
HKR05A,CA | 24 / 27 | 30 / 30 | 4.75 / 16,200 | ||||
HKR08A,CA | 34 / 39 | 40 / 40 | 7.0 / | 23,800 | |||
HKR10A,CA | 45 / 52 | 60 / 60 | 9.5 / | 32,400 | |||
HKR15A,CA | 45 / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 | / 48,600 | |
GPC1536M41* |
|
|
|
|
|
| |
HKR05A,CA | 24 / 27 | 30 / 30 | 4.75 / 16,200 | ||||
HKR08A,CA | 34 / 39 | 40 / 40 | 7.00 / 23,800 | ||||
HKR10A,CA | 45 / 52 | 60 / 60 | 9.50 / 32,400 | ||||
HKR15A,CA | 45 / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 | / 48,600 | |
GPC1542M41* |
|
|
|
|
|
| |
HKR05A,CA | 24 / 27 | 30 / 30 | 4.75 / 16,200 | ||||
HKR08A,CA | 34 / 39 | 40 / 40 | 7.0 / | 23,800 | |||
HKR10A,CA | 45 / 52 | 60 / 60 | 9.5 / | 32,400 | |||
HKR15A,CA | 45 / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 | / 48,600 | |
GPC1548M41* |
|
|
|
|
|
| |
HKR05A,CA | 25 / 28 | 30 / 30 | 4.75 / 16,200 | ||||
HKR08A,CA | 34 / 40 | 40 / 40 | 7.00 / 23,800 | ||||
HKR10A,CA | 46 / 53 | 60 / 60 | 9.50 / 32,400 | ||||
HKR15A,CA | 46 / 52 | 60 / 60 | 22 / 25 | 30 / 30 | 14.25 | / 48,600 | |
HKR20A,CA | 46 / 52 | 60 / 60 | 43 / 49 | 60 / 60 | 19.50 | / 66,500 |
IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.
Heating kW Correction Factor
Supply Votage | 240 | 230 | 220 | 210 | 208 |
|
|
|
|
|
|
Correction Factor | 1.0 | 0.93 | 0.85 | 0.78 | 0.76 |
Multiply rated kW by correction factor to get actual kW
All wires and overcurrent protection devices are sized for use with electric heaters only and without WARNING refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent
protection during refrigeration cycle.