Goodman Mfg GPC15 SEER service manual GPC1524-48M41, HKR Electrical Data

Page 6

PRODUCT DESIGN

 

 

GPC15[24-48]M41*

HKR ELECTRICAL DATA

 

 

 

 

 

 

 

 

 

 

 

 

Circuit #1

Circuit #2

 

 

 

Minimum Circuit

Maximum

Minimum Circuit

Maximum

Actual

Model and Heat Kit Usage

Overcurrent

Overcurrent

kW & BTU

Ampacity

Ampacity

 

Protection (amps)

Protection (amps)

at 240V

 

at 208 / 240V

at 208 / 240V

 

at 208 / 240V

at 208 / 240V

 

 

 

 

 

 

 

GPC1524M41*

 

 

 

 

 

 

HKR05A,CA

24 / 27

30 / 30

----

----

4.75 / 16,200

HKR08A,CA

33 / 28

40 / 40

----

----

7.00 / 23,800

HKR10A,CA

45 / 51

60 / 60

----

----

9.50 / 32,400

GPC1530M41*

 

 

 

 

 

 

HKR05A,CA

24 / 27

30 / 30

--

--

4.75 / 16,200

HKR08A,CA

34 / 39

40 / 40

--

--

7.0 /

23,800

HKR10A,CA

45 / 52

60 / 60

--

--

9.5 /

32,400

HKR15A,CA

45 / 52

60 / 60

22 / 25

30 / 30

14.25

/ 48,600

GPC1536M41*

 

 

 

 

 

 

HKR05A,CA

24 / 27

30 / 30

----

----

4.75 / 16,200

HKR08A,CA

34 / 39

40 / 40

----

----

7.00 / 23,800

HKR10A,CA

45 / 52

60 / 60

----

----

9.50 / 32,400

HKR15A,CA

45 / 52

60 / 60

22 / 25

30 / 30

14.25

/ 48,600

GPC1542M41*

 

 

 

 

 

 

HKR05A,CA

24 / 27

30 / 30

--

--

4.75 / 16,200

HKR08A,CA

34 / 39

40 / 40

--

--

7.0 /

23,800

HKR10A,CA

45 / 52

60 / 60

--

--

9.5 /

32,400

HKR15A,CA

45 / 52

60 / 60

22 / 25

30 / 30

14.25

/ 48,600

GPC1548M41*

 

 

 

 

 

 

HKR05A,CA

25 / 28

30 / 30

----

----

4.75 / 16,200

HKR08A,CA

34 / 40

40 / 40

----

----

7.00 / 23,800

HKR10A,CA

46 / 53

60 / 60

----

----

9.50 / 32,400

HKR15A,CA

46 / 52

60 / 60

22 / 25

30 / 30

14.25

/ 48,600

HKR20A,CA

46 / 52

60 / 60

43 / 49

60 / 60

19.50

/ 66,500

IMPORTANT NOTE: A separate power supply is required for the HKR heater kit.

Heating kW Correction Factor

Supply Votage

240

230

220

210

208

 

 

 

 

 

 

Correction Factor

1.0

0.93

0.85

0.78

0.76

Multiply rated kW by correction factor to get actual kW

All wires and overcurrent protection devices are sized for use with electric heaters only and without WARNING refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum overcurrent

protection during refrigeration cycle.

6

Image 6
Contents Technical Manual Product Identification Goodman will not be responsibleFor any injury or property damage GPC1524M41A GPC1530M41A GPC1536M41A GPC1542M41A GPC1548M41A Product Design Location and ClearancesRooftop Installation Multi-positional M GPC1524-48M41 HKR Electrical DataProduct Dimensions Control Connection Wire NPT Female EntranceGPC1524-48M41A ElectricalAccessories Accessories GPC/GPH****M ModelsBlower Performance Data Performance Data Formulas105 115 Cooling Performance DataGPC1524M41 21.2KW = Total system power 147GPC1530M41 AirflowExpanded Performance Data 146GPC1536M41 148 GPC1542M41 152 Is Ahri Rating Conditions KW =GPC1548M41 45.5 Performance Test Wiring Diagrams HKRGPC1524-48M41 Diagrams Wiring