Goodman Mfg 000 &12, MSC/MSH 9, 000 BTUH + 115 Volt important safety instructions Electrical

Page 7

2.Insert tube in flare tool to measurement “A” in chart. Flare tubing as shown in Figure 19. Make sure flare is free of burrs and completely formed to make a leak proof joint.

NOTE: In order to avoid dropping burrs into the tubing, angle the end of the copper tube/pipe in a downward direction as you remove the burrs.

Pipe

Reamer

Point down

Figure 17

 

 

 

 

Outdoor

 

 

Tightening

 

 

 

 

 

 

Additional

 

 

 

 

 

 

 

 

Torque

 

 

 

 

 

 

Tightening

Diameter (mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(N. cm)

 

 

 

 

Torque (N. cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/4" (Φ 6.35)

1500

 

 

 

 

 

1600

 

 

 

 

 

 

 

 

 

(153kgf.cm)

 

 

 

 

 

 

(163kgf.cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/8" (Φ 9.52)

2500

 

 

 

 

 

2500

 

 

 

 

 

 

 

 

 

(255kgf.cm)

 

 

 

 

 

 

(265kgf.cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2" (Φ12.7)

2500

 

 

 

 

 

3600

 

 

 

 

 

 

 

 

 

(255kgf.cm)

 

 

 

 

 

 

(367kgf.cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flare nut

Figure 20

Copper tube

Figure 18

4.Flare Connections: Firmly hold the copper pipe in a die with the dimensions as in the following table.

 

Outdoor

A (inches & mm)

Model

Diameter

 

 

 

(inches & mm)

Max.

Min.

MS* 09 & 12

1/4" (Φ 6.35)

3/64" (1.3)

1/32" (0.7)

 

 

 

 

MS*09

3/8" (Φ 9.52)

1/16" (1.6)

3/64" (1.0)

 

 

 

 

MS*12

1/2" (Φ12.7)

1/16" (1.8)

3/64" (1.0)

 

 

 

 

Figure 21

Do not over-tighten. Excessive torque can break the nut and/or crimp the pipe.

Electrical

 

"A"

Handle

Bar

Bar

 

 

 

Yoke

 

 

Cone

Copper pipe

Clamp handle

Red arrow mark

Figure 19

5.Tightening the connection:

Align the center of the pipes and finger-tighten the flare nut. Using a spanner and torque wrench (Figures 20 & 21) continue tightening the flare nut until the nut is firmly on the pipe.

HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury or death due to electric shock. Wiring must conform with NEC or CEC and all local codes. Undersized wires could cause poor equipment performance, equipment damage or fire.

7

Image 7
Contents Shipping Inspection Installation & Operations ManualCodes & Regulations Installation ConsiderationsIndoor Unit Installation Rooftop InstallationsTools Refrigerant Piping & Condensate Piping Installation Indoor Unit Installation Outdoor Unit InstallationRefrigerant Pipe Connection MS* 9 & MS*12 Mounting DimensionsElectrical Connect the Cable to the Indoor Unit Connect the Cable to the Outdoor UnitSystem Evacuation Leak Testing Nitrogen or Nitrogen-TracedSafe Refrigerant Handling Safety CheckTest Running Goodman Manufacturing Company, L.P

000 BTUH + 115 Volt, 000 &12, MSC/MSH 9 specifications

Goodman Manufacturing is a renowned brand in the HVAC industry, known for its reliable and efficient heating and cooling solutions. Among their offerings, the Goodman MSC/MSH series, specifically the 9,000 and 12,000 BTUH models, stand out as highly effective, compact air conditioning units designed for residential and light commercial applications.

These units provide a reliable cooling solution with a modest 115-volt electrical supply, making them suitable for various settings without the need for significant electrical upgrades. The Goodman MSC/MSH units employ advanced refrigerant technology, ensuring efficient heat exchange and optimal energy usage. The units feature a SEER (Seasonal Energy Efficiency Ratio) rating that meets or exceeds modern energy efficiency standards, helping homeowners save on electricity bills while reducing their carbon footprint.

A key characteristic of the MSC/MSH series is their compact design, which allows for easy installation in tight spaces. The lightweight construction simplifies transport and handling, making it easier for HVAC professionals to install these units in challenging locations like attics, closets, or small commercial areas. Additionally, these models are equipped with a durable cabinet that is designed to withstand the elements, including corrosion-resistant materials that ensure longevity and reliability.

The Goodman MSC/MSH series features an innovative multi-speed fan that provides enhanced airflow while operating quietly, contributing to a comfortable indoor environment. Furthermore, with their user-friendly controls, these units allow for easy temperature adjustments, ensuring that users can maintain their desired indoor climate with minimal effort.

Another notable technology within these models is the inclusion of a scroll compressor, which is known for its efficiency and durability. This compressor type is quieter compared to traditional reciprocating models, further adding to the comfort of the living space. The MSC/MSH series also includes a built-in safety switch designed to prevent the unit from running in unsafe conditions, thereby extending the life of the system and enhancing user safety.

In summary, Goodman Manufacturing's MSC/MSH 9,000 and 12,000 BTUH models provide a reliable, efficient, and versatile cooling solution, making them a favorable choice for homeowners and light commercial users alike. With advanced technology, user-friendly features, and a commitment to durability, these units exemplify Goodman’s dedication to quality and performance in the HVAC market.