Goodman Mfg R-410A service manual Cooling Performance Data, GPC1424H41A, 105 115

Page 13

13

MODEL: GPC1424H41A*

 

 

 

 

EXPANDED PERFORMANCE DATA

 

 

 

COOLING OPERATION

 

Design Subcooling, 9 ± 2°F @ the liquid access fitting connection AHRI 95 test conditions. Design Superheat 5 ± 2°F @ the compressor suction access fitting connection.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

 

75

 

 

 

 

85

 

 

 

95

 

 

105

 

 

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entering Indoor Wet

Bulb Temperature

 

 

 

 

 

 

 

 

 

IDB*

Airflow

 

59

63

 

67

71

59

63

 

67

71

59

63

 

67

71

59

63

 

67

71

59

63

67

71

59

63

67

71

 

 

MBh

24.1

25.0

 

27.4

-

23.5

24.4

 

26.7

-

23.0

23.8

 

26.1

-

22.4

23.2

 

25.5

-

21.3

22.1

24.2

-

19.7

20.5

22.4

-

 

 

S/T

0.74

0.62

0.43

-

0.77

0.64

 

0.45

-

0.79

0.66

0.46

-

0.82

0.68

0.47

-

0.85

0.71

0.49

-

0.85

0.71

0.49

-

 

 

Delta T

17

15

11

-

17

15

 

11

-

17

15

11

-

18

15

12

-

17

15

11

-

16

14

11

-

 

955

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

1.57

1.60

1.66

-

1.70

1.73

 

1.79

-

1.81

1.85

1.91

-

1.91

1.95

2.02

-

1.99

2.04

2.11

-

2.06

2.11

2.19

-

 

 

AMPS

6.6

6.8

7.0

-

7.1

7.3

 

7.5

-

7.7

7.9

8.1

-

8.2

8.4

8.7

-

8.7

8.9

9.2

-

9.2

9.4

9.7

-

 

 

HI PR

233

251

265

-

262

282

 

298

-

298

321

338

-

339

365

386

-

382

411

434

-

422

454

479

-

 

 

LO PR

111

118

129

-

118

125

 

137

-

122

130

142

-

128

137

149

-

135

143

156

-

139

148

162

-

 

 

MBh

23.4

24.3

26.6

-

22.9

23.7

 

26.0

-

22.3

23.1

25.3

-

21.8

22.6

24.7

-

20.7

21.4

23.5

-

19.2

19.9

21.8

-

 

 

S/T

0.71

0.59

0.41

-

0.73

0.61

 

0.42

-

0.75

0.63

0.44

-

0.78

0.65

0.45

-

0.81

0.67

0.47

-

0.81

0.68

0.47

-

 

 

Delta T

18

16

12

-

18

16

 

12

-

18

16

12

-

18

16

12

-

18

16

12

-

17

15

11

-

70

850

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KW

1.56

1.59

1.64

-

1.68

1.72

 

1.78

-

1.79

1.83

1.90

-

1.89

1.93

2.00

-

1.97

2.02

2.09

-

2.05

2.09

2.17

-

 

 

AMPS

6.6

6.7

6.9

-

7.1

7.2

 

7.5

-

7.7

7.8

8.1

-

8.1

8.3

8.6

-

8.6

8.8

9.1

-

9.1

9.3

9.6

-

 

 

HI PR

231

249

263

-

259

279

 

295

-

295

317

335

-

336

361

382

-

378

407

429

-

418

449

474

-

 

 

LO PR

110

117

128

-

116

124

 

135

-

121

129

141

-

127

135

148

-

133

142

155

-

138

147

160

-

 

 

MBh

21.6

22.4

24.5

-

21.1

21.9

 

24.0

-

20.6

21.3

23.4

-

20.1

20.8

22.8

-

19.1

19.8

21.7

-

17.7

18.3

20.1

-

 

 

S/T

0.68

0.57

0.40

-

0.71

0.59

 

0.41

-

0.73

0.61

0.42

-

0.75

0.63

0.43

-

0.78

0.65

0.45

-

0.78

0.66

0.45

-

 

745

Delta T

18

16

12

-

18

16

 

12

-

18

16

12

-

19

16

12

-

18

16

12

-

17

15

11

-

 

KW

1.52

1.55

1.60

-

1.64

1.68

 

1.73

-

1.75

1.79

1.85

-

1.84

1.88

1.95

-

1.92

1.97

2.03

-

1.99

2.04

2.11

-

 

 

AMPS

6.4

6.6

6.8

-

6.9

7.1

 

7.3

-

7.5

7.6

7.9

-

7.9

8.1

8.4

-

8.4

8.6

8.9

-

8.9

9.1

9.4

-

 

 

HI PR

224

241

255

-

252

271

 

286

-

286

308

325

-

326

351

370

-

367

394

417

-

405

436

460

-

 

 

LO PR

107

114

124

-

113

120

 

131

-

117

125

136

-

123

131

143

-

129

137

150

-

134

142

155

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

24.5

25.2

27.3

29.3

23.9

24.7

 

26.7

28.6

23.4

24.1

26.0

28.0

22.8

23.5

25.4

27.3

21.7

22.3

24.1

25.9

20.1

20.7

22.4

24.0

 

 

S/T

0.84

0.76

0.57

0.37

0.88

0.78

 

0.59

0.38

0.90

0.80

0.61

0.39

0.93

0.83

0.63

0.40

0.96

0.86

0.65

0.42

0.97

0.87

0.66

0.42

 

955

Delta T

20

18

15

10

20

19

 

15

11

20

19

15

11

20

19

15

11

20

18

15

10

19

17

14

10

 

KW

1.58

1.62

1.67

1.73

1.71

1.75

 

1.81

1.87

1.82

1.87

1.93

2.00

1.92

1.97

2.04

2.11

2.01

2.06

2.13

2.20

2.08

2.13

2.20

2.28

 

 

AMPS

6.7

6.8

7.1

7.3

7.2

7.4

 

7.6

7.9

7.8

8.0

8.2

8.5

8.3

8.5

8.7

9.1

8.8

9.0

9.3

9.6

9.3

9.5

9.8

10.2

 

 

HI PR

236

254

268

279

265

285

 

301

314

301

324

342

357

343

369

389

406

386

415

438

457

426

458

484

505

 

 

LO PR

112

120

131

139

119

126

 

138

147

123

131

143

153

130

138

151

160

136

145

158

168

141

150

163

174

 

 

MBh

23.8

24.5

26.5

28.5

23.2

23.9

 

25.9

27.8

22.7

23.4

25.3

27.1

22.1

22.8

 

24.7

26.5

21.0

21.7

23.4

25.2

19.5

20.1

21.7

23.3

 

 

S/T

0.81

0.72

0.55

0.35

0.83

0.75

 

0.57

0.36

0.86

0.77

0.58

0.37

0.88

0.79

 

0.60

0.38

0.92

0.82

0.62

0.40

0.92

0.83

0.63

0.40

75

850

Delta T

21

19

16

11

21

19

 

16

11

21

19

16

11

21

19

 

16

11

21

19

16

11

19

18

15

10

KW

1.57

1.60

1.66

1.71

1.70

1.73

 

1.79

1.85

1.81

1.85

1.91

1.98

1.91

1.95

 

2.02

2.09

1.99

2.04

2.11

2.18

2.06

2.11

2.19

2.26

 

 

AMPS

6.6

6.8

7.0

7.2

7.1

7.3

 

7.5

7.8

7.7

7.9

8.1

8.4

8.2

8.4

 

8.7

9.0

8.7

8.9

9.2

9.5

9.2

9.4

9.7

10.1

 

 

HI PR

233

251

265

277

262

282

 

298

310

298

321

339

353

339

365

 

386

402

382

411

434

452

422

454

479

500

 

 

LO PR

111

118

129

138

118

125

 

137

145

122

130

142

151

128

137

 

149

159

135

143

156

166

139

148

162

172

 

 

MBh

22.0

22.6

24.5

26.3

21.5

22.1

 

23.9

25.7

20.9

21.6

23.3

25.1

20.4

21.0

 

22.8

24.4

19.4

20.0

21.6

23.2

18.0

18.5

20.0

21.5

 

 

S/T

0.78

0.69

0.53

0.34

0.81

0.72

 

0.55

0.35

0.83

0.74

0.56

0.36

0.85

0.76

0.58

0.37

0.88

0.79

0.60

0.39

0.89

0.80

0.60

0.39

 

745

Delta T

21

19

16

11

21

20

 

16

11

21

20

16

11

21

20

16

11

21

20

16

11

20

18

15

10

 

KW

1.53

1.56

1.61

1.67

1.65

1.69

 

1.75

1.81

1.76

1.80

1.86

1.93

1.86

1.90

1.97

2.03

1.94

1.98

2.05

2.12

2.01

2.06

2.13

2.20

 

 

AMPS

6.5

6.6

6.8

7.1

7.0

7.1

 

7.3

7.6

7.5

7.7

7.9

8.2

8.0

8.2

8.4

8.7

8.5

8.7

9.0

9.3

9.0

9.2

9.5

9.8

 

 

HI PR

226

244

257

268

254

273

 

289

301

289

311

328

343

329

354

374

390

370

398

421

439

409

440

465

485

 

 

LO PR

108

115

125

134

114

121

 

133

141

119

126

138

147

125

133

145

154

131

139

152

161

135

144

157

167

 

* IDB: Entering Indoor Dry Bulb Temperature

 

 

 

NOTE: Shaded area is ACCA (TVA) conditions

 

 

 

 

 

 

 

 

 

 

 

 

High and low pressures are measured at the liquid and suction access fittings.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COOLING PERFORMANCE DATA

GPC1424H41A*

Image 13
Contents Technical Manual Goodman will not be responsible Product IdentificationFor any injury or property damage Do not connect or use any device Product Design Outside Slab Installation Horizontal HRooftop Installation Horizontal H Overcurrent Minimum Circuit MaximumAmpacity Protection amps At 208GPC1424-60H41A Product DimensionsGPC1424H41 GPC1430H41 GPC1436H41 Package Cooling SpecificationsGPC1442H41 GPC1448H41 GPC1460H41 Package Cooling SpecificationsAccessories GPC/GPH****H Units AccessoriesDry Coil Data Blower Performance DataFormulas Performance DataGPC1424H41A Cooling Performance Data105 115 151 Expanded Performance DataAirflow GPC1430H41A10.5 10.8 11.2 GPC1436H41A Is Ahri Rating Conditions 145GPC1442H41A 148 GPC1448H41A 149 GPC1460H41A 146 Performance Test GPC1424-60H41A Wiring Diagrams
Related manuals
Manual 47 pages 31.4 Kb

R-410A specifications

Goodman Manufacturing, a well-respected name in the HVAC industry, has made significant advancements with their R-410A refrigerant technology. R-410A, a hydrofluorocarbon (HFC), has positioned itself as a superior alternative to the older R-22 refrigerant, which has been phased out due to its ozone-depleting properties. Goodman’s commitment to energy efficiency and environmental sustainability is well reflected in their use of R-410A in their air conditioning and heat pump systems.

One of the main features of Goodman’s R-410A systems is their exceptional energy efficiency. The R-410A refrigerant operates at a higher pressure than R-22, which allows for better heat transfer and improved cooling capacity. This results in reduced energy consumption and lower utility bills for consumers. Goodman’s air conditioning units designed for use with R-410A are often rated with high Seasonal Energy Efficiency Ratio (SEER) ratings, making them an eco-friendly choice for residential and commercial applications.

Another notable technology employed by Goodman is their commitment to reliable performance through advanced compressor designs. Goodman's scroll compressors are optimized for R-410A, ensuring quieter operation and reducing vibration levels. These compressors are known for their efficiency and longevity, making them a favorite among homeowners seeking dependable and durable climate control solutions.

Goodman's multi-stage cooling systems that utilize R-410A offer precise temperature control and enhanced comfort. By controlling the speed of the compressor, Goodman’s units can adjust output according to the heating or cooling demand, maximizing comfort while minimizing energy waste. This adaptability not only enhances indoor air quality but also contributes to a greener environment by using less energy.

Furthermore, Goodman incorporates high-tech diagnostic controls into their systems. These controls provide real-time performance data, allowing homeowners and technicians to monitor system status and troubleshoot issues more easily. By using R-410A combined with these innovative technologies, Goodman emphasizes reliability and user-friendly operation.

In conclusion, Goodman Manufacturing’s use of R-410A refrigerant reflects their dedication to efficiency, reliability, and environmental stewardship in HVAC solutions. The combination of advanced compressor technologies, high energy efficiency, and innovative controls solidifies Goodman’s reputation as a leader in the industry, offering homeowners and businesses the comfort and peace of mind they deserve.