Roof Curb Installation — Rigging

Provisions for forks have been included in the unit base frame. No other fork locations are approved.

Unit must be lifted by the four lifting holes located at the base frame corners.

Lifting cables should be attached to the unit with shackles.

The distance between the crane hook and the top of the unit must not be less than 60”.

Two spreader bars must span over the unit to prevent damage to the cabinet by the lift cables. Spreader bars must be of sufficient length so that cables do not come in contact with the unit during transport. Remove wood struts mounted beneath unit base frame before set- ting unit on roof curb. These struts are intended to protect unit base frame from fork lift damage. To remove the struts, extract the sheet metal retainers and pull the struts through the base of the unit. Refer to rigging label on the unit.

Important: If using bottom discharge with roof curb, duct-work should be attached to the curb prior to installing the unit. Duct-work dimensions are shown in Roof Curb Installation Instructions Manual.

Refer to the Roof Curb Installation Instructions for proper curb installation. Curbing must be installed in compliance with the National Roofing Contractors Association Manual.

Lower unit carefully onto roof mounting curb. While rigging the unit, the center of gravity will cause the condenser end to be lower than the supply air end.

Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, take care to center the unit. Check for proper alignment and orientation of supply and return openings with duct.

40”

 

Compressor 1

 

 

 

 

 

 

 

Coil

 

 

 

 

 

 

Evaporator

 

Return

Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor 2

58”

Corner & Center-of-Gravity Locations

15-Ton Units

Weights

(lbs.)

 

Corner Weight A

570

Corner Weight B

535

Corner Weight C

545

Corner Weight D

510

Shipping Weight

2270

Operating Weight

2155

20-Ton Units

Weights

(lbs.)

 

Corner Weight A

655

Corner Weight B

535

Corner Weight C

600

Corner Weight D

485

Shipping Weight

2390

Operating Weight

2275

To assist in determining rigging requirements, unit weights are shown to the right. Note: These weights are calculated without installed accessories.

14

www.goodmanmfg.com

SS-CPG180-240

Image 14
Contents CPG Commercial Nomenclature ConfiguraonProduct Features Standard FeaturesCPG180350 Cooling Capacity Operating Weight lbsShip Weight lbs Heating CapacityCPG240 4003B 4004B 4007B Cooling Capacity Evaporator Motor / CoilTurns Open Airflow Data 15 TonsStandard Belt Drive ― Down Shot High-Static Belt Drive ― Down ShotAirflow Data 20 Tons 6075 Ata 15 TonsAirflow 5400390 Expanded Cooling Data 15 Tons180.0 1397000 Ata 20 Tons7875 5600 448 Expanded Cooling Data 20 Tons 240.0 13488⁷/₃₂ 133½ 50⁹/₃₂ ⁵/₃₂ DimensionsGas Inlet Location ¾ NPT Vertical Discharge Top of Unit12¹/₈ ³/₅ High-Voltage EntranceLow ⁴/₅ Entrance Unit ClearancesElectrical Entrance Locations Ton Units Weights Lbs Roof Curb Installation RiggingCorner & Center-of-Gravity Locations Ton Units Weights Lbs 77½ Curb Bottom O.D Roof Curb InstallationCurb Top O.D 119¾ Curb Top O.D 17²/₂₅ Power death Product Specifications Product Specifications Product Specifications All Models AccessoriesItem # Description Fits Model Sizes