Troubleshooting
Symptom | Possible Cause | Corrective Action | |
|
|
| |
| Blown fuse or open circuit breaker | Replace fuse or reset circuit breaker and check amps | |
|
|
| |
Blower fails to | Broken fan belt | Replace | |
operate | Defective motor or capacitor | Replace | |
| |||
|
|
| |
| Motor starter overloaded | Reset starter and check amps | |
|
|
| |
| Airflow too high | Check airflow and adjust drives if needed | |
|
|
| |
| Static pressures are higher or lower | If higher, ductwork should be improved | |
| than design | If lower, fan RPMs should be lower | |
|
|
| |
Motor overamps | Blower rotation is incorrect | Check rotation and correct | |
|
| ||
Motor voltage incorrect | Check motor nameplate and supplied voltage | ||
| |||
|
|
| |
| Motor horsepower too low | See specifications and catalog for fan curves to determine | |
| if horsepower is sufficient | ||
|
| ||
|
|
| |
| Shorted windings in motor | Replace motor | |
|
|
| |
| Mixing box damper not fully open | Adjust damper linkage or replace damper motor | |
|
|
| |
| System static pressure too high | Improve ductwork to eliminate losses using good duct | |
| practices | ||
|
| ||
|
|
| |
| Blower speed too low | Check for correct drives and RPMs with catalog data | |
|
|
| |
Insufficient airflow | Mixing box dampers closed | Open and adjust | |
|
| ||
Dirty or clogged filters | Clean or replace | ||
| |||
|
|
| |
| Leaks in ductwork | Repair | |
|
|
| |
| Elbows, or other obstructions may | Correct or improve ductwork | |
| restrict fan outlet | ||
|
|
| |
| Belt slippage | Adjust belt tension | |
|
|
| |
| Blower fan speed too high | Check for correct fan RPM | |
|
|
| |
Too much airflow | Filter(s) not in place | Install filters | |
|
| ||
Insufficient static pressure | Induce static pressure into system ductwork | ||
| |||
| (airflow resistance) | ||
|
| ||
|
|
| |
| Wheel rubbing on housing | Center wheel | |
|
|
| |
| Loose wheel on shaft | Tighten wheel setscrew | |
|
|
| |
| Loose motor or blower sheave | Tighten sheave setscrew | |
|
|
| |
| Belts too loose | Adjust belt tension after 24 hours of operation | |
|
|
| |
| Belts too tight | Loosen to maintain 3/8 inch deflection per ft. of span | |
| between sheaves | ||
|
| ||
|
|
| |
Excessive noise | Worn belt | Replace | |
|
| ||
|
| ||
or vibration | Motor base or blower loose | Tighten mountings bolts | |
|
|
| |
| Worn bearings | Replace | |
|
|
| |
| Bearing and drive alignment | Realign | |
|
|
| |
| Motor out of balance | Replace | |
|
|
| |
| Wheel out of balance | Replace or rebalance | |
|
|
| |
| Sheaves eccentric or | Replace or rebalance | |
|
|
| |
| Accumulation of material on wheel | Clean wheel and housing | |
|
|
|
10 Model VFCD/VFCB Vertical Fan Coil
®