Honeywell TE532ELW user manual Battery Installation Remote Sensor, Main Unit, Weather Display

Page 3

NOTE: When the temperature falls below freezing, the batteries in the outdoor remote sensor may have reduced voltage supply and a shorter effective range. We recommend using lithium batteries at temperatures of 32°F (0°C) and below.

BATTERY INSTALLATION REMOTE SENSOR

NOTE: Install the batteries; select the channel and temperature in °C or °F before mounting the remote sensor.

Remove the screws from the battery compartment with a small Phillips screwdriver.

Set the channel. The switch is located in the battery compartment. Channel 1 is typically selected if only one remote sensor is being used.

Install 2 “AAA” size alkaline batteries (not included) matching the polarities shown in the battery compartment.

Replace the battery compartment door and secure the screws.

Secure the remote sensor in the desired location.

MAIN UNIT

Remove the battery compartment door.

Install 2 batteries (UM-3 or “AA” size 1.5V) matching the polarity as shown in the battery compartment.

Replace the battery compartment door.

LOW BATTERY WARNING

A low-battery indicator [] will appear next to the indoor or remote data reading line of the main unit warning that the corresponding batteries need replacement.

9

GETTING STARTED

WEATHER DISPLAY

After batteries are installed; remote sensor will transmit temperature and humidity data at 45 second intervals. The main unit may take up to two minutes to receive the initial readings. Upon successful reception, remote temperature will appear under the weather forecast section of the main unit’s display (the default remote channel is channel one). The main unit will automatically update readings at 45- second intervals.

After communication between the main unit and remote sensor has been established, secure the remote sensor in the desired location.

If no signal is received from the remote sensor within two minutes, dashes [- - -] will be displayed. Press and hold the DOWN ( ) button on the main unit for two seconds to initiate another signal search.

PLACEMENT OF THE UNITS

The main unit can be placed on any flat surface indoors. The remote sensor can be placed indoors or outdoors, on a flat surface or mounted on the wall.

10

REMOTEAND INDOOR TEMPERATURE & HUMIDITY The remote temperature and humidity information line is located right below the weather forecast line of the main unit’s display.

The wave icon is located above the remote channel number indicates the reception status from the corresponding remote sensor.

There are three following types of the reception status may be displayed:

The unit is in a searching mode.

Temperature and readings is securely registered.

No signals detected.

- - -

 

 

 

The indoor temperature and humidity with the icon

is

located below the remote temperature and humidity information line.

NOTE: If the indoor or remote temperature or humidity goes above or below operating range stated in specifications, the main unit’s display ( weather) will show dashes “- - -” on the corresponding line.

AUTO-SCANNING

Press and hold the CHANNEL button for 2 seconds – the icon “ ” will appear on the main unit display to the left of the COMFORT LEVEL indicator.

All three remote channels data will be displayed one-by- one automatically with 11 seconds delay in the following sequence: Channel 1, Channel 2 and Channel 3.

To exit from scanning mode, press and hold the CHANNEL button for 2 seconds, and the icon “ ” will disappear, returning the main unit display to the default display mode.

11

PROGRAMMABLE TEMPERATURE ALARM

This product allows manual programming of a HIGH and LOW temperature alarms for all three remote channels at the same time. Once the actual remote temperature will reach the pre-set high or low limits, the alarm will sound. The alarm can be set for temperature readings between -58 °F and 158°F.

To program the temperature alarm for all three remote channels,

Press the TEMP AL button once to enter into the High Temperature Alarm programming mode – the abbreviation “OF” with the high temperature limit symbol ( ) will be displayed on the remote temperature line

Press and hold TEMP AL button until the abbreviation “OF” will flash

Use UP( ) or DOWN( ) arrow buttons to adjust the higher temperature limit

Press the TEMP AL button to confirm the selected value

Press the TEMP AL button once to enter into the Low Temperature Alarm programming mode – the abbreviation “OF” with the low temperature limit symbol ( ) will be displayed on the remote temperature line

Press and hold TEMP AL button until the abbreviation “OF” will flash

Use UP( ) or DOWN( ) arrow buttons to adjust the lower temperature limit

Press the TEMP AL button to confirm the selected value

12

Image 3
Contents Main Unit Table of ContentsFeatures Introduction Product OverviewFRONT/REAR View Battery Installation Remote Sensor Main UnitWeather Display Lost Communication Comfort Level IndicatorsWeather Forecast Maximum and Minimum ReadingsTime Zone Setting the Weekday W and Single DAY SAlarms Activating the AlarmSpecifications Declaration of Conformity Standard Warranty InformationFCC Statement