Goodman Mfg GSC140421A, GSH140301A, GSH140241A, GSH140181A, GSH140361A, RT6213004 Performance Test

Page 24

PERFORMANCE DATA

PERFORMANCE TEST

All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets:

If conditions vary from this, results will change as follows:

1.As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and high side pressures and power will not change.

2.As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will occur in low and high side pressures and power.

A properly operating unit should be within plus or minus 2 degrees of the subcooling value shown in the Heat Pump Specifications.

A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.

A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.

A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.

A properly operating unit should be within plus or minus 3 Amps of the typical value shown.

NOTE: Pressures are measured at the liquid and suction service valve ports.

24

Image 24
Contents Technical Information Manual 036 Product IdentificationProduct Identification Product Design AA AAHeat Pump Specifications GSH14018-0601ACooling Performance Data GSH140181ACooling Operation 105 115 Entering Indoor Wet 22.611.7 212GSH140241A Airflow 26.7217 25.9GSH140301A 27.7GSH140361A 11.8 12.2 12.6 GSH140421A 37.836.7 33.9168 177 185 191 43.9 20542.6 203GSH140481A 44.553.0 15.851.4 15.6GSH140601A 55.516.3 221Performance Data Split System Heating Performance Expanded Performance DataModel GSH140421A* / CA*F4860D6A*+TXV / MBR2000**-1 Heating Specifications Capacity Btuh 14.4 19.2Performance Test Wiring Diagrams