HEAT PUMP SPECIFICATIONS |
|
Cooling Capacity, BTUH
Compressor
R.L. Amps
L.R. Amps
Loss of Charge Pressure Switch
Open / Close
Condenser Fan Motor
Horsepower
F.L. Amps
Liquid Line, Inches O.D.
Suction Line, Inches O.D.
Refrigerant Charge
Power Supply
Minimum Circuit Ampacity(1)
Maximum Overcurrent Device(2)
Electrical Conduit Size
Power Supply (Inches)
Approximate Shipping Weight
GSH140181A* | GSH140241A* | GSH140301A* | GSH140361A* | GSH140421A* | GSH140481A* | GSH140601A* |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
18,000 | 24,000 | 28,000 | 34,600 | 39,600 | 46,000 | 55,000 |
|
|
|
|
|
|
|
9 | 10.9 | 12.2 | 13.4 | 16 | 18.3 | 19.8 |
41.0 | 54.0 | 63.0 | 73.0 | 88.0 | 109.0 | 137.0 |
7 PSIG/25 PSIG | 7 PSIG/25 PSIG | 7 PSIG/25 PSIG | 7 PSIG/25 PSIG | 7PSIG/25 PSIG | 7 PSIG/25 PSIG | 7PSIG/25 PSIG |
1/12 | 1/6 | 1/6 | 1/4 | 1/4 | 1/4 | 1/4 |
0.6 | 1.1 | 1.1 | 1.5 | 1.5 | 1.5 | 1.5 |
3/8" | 3/8" | 3/8" | 3/8" | 3/8" | 3/8" | 3/8" |
3/4" | 3/4" | 3/4" | 7/8" | 7/8" | 7/8" | 7/8" |
160 | 160 | 165 | 220 | 220 | 280 | 285 |
11.8 | 14.7 | 16.3 | 18.3 | 21.5 | 27.8 | 27.3 |
20 | 20 | 20 | 30 | 30 | 40 | 40 |
1/2 or 3/4 | 1/2 or 3/4 | 1/2 or 3/4 | 1/2 or 3/4 | 1/2 or 3/4 | 1/2 or 3/4 | 1/2 or 3/4 |
199 | 207 | 207 | 242 | 242 | 266 | 280 |
(1)Wire size should be determined in acordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
(2)May use fuses or HACR type Circuit Breakers of the same size as noted.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/ circuit breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.