Goodmans GSH 13 SEER - 3 Phase Split System Heat Pump, RT6212008x5 Heating Performance Data, 24.9

Page 23

HEATING PERFORMANCE DATA

 

GSH130[36-48]3AE;GSH130363AF

 

 

 

 

 

 

 

EXPANDED PERFORMANCE DATA

 

 

GSH130603AC

 

 

 

 

 

 

 

 

 

 

 

 

 

MODEL: GSH13036-3AE / ARUF49-00*-1* / ARUF36421A*

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

 

MBh

40.2

38.1

35.8

33.5

32.0

31.0

28.8

26.6

19.9

18.4

16.9

16.0

15.4

13.8

12.3

10.7

9.1

7.5

 

Delta T

29.2

27.7

26.0

24.3

23.2

22.5

20.9

19.3

14.5

13.4

12.3

11.6

11.2

10.0

8.9

7.8

6.6

5.4

 

KW

2.80

2.75

2.70

2.64

2.61

2.59

2.54

2.49

2.47

2.41

2.36

2.33

2.31

2.25

2.20

2.15

2.09

2.04

 

AMPS

11.0

10.2

9.6

9.1

8.7

8.6

8.1

7.7

7.4

7.1

6.8

6.6

6.5

6.2

5.8

5.5

5.1

4.7

 

COP

4.20

4.05

3.89

3.71

3.58

3.50

3.32

3.13

2.36

2.23

2.10

2.01

1.95

1.79

1.63

1.46

1.27

1.07

 

EER

14.4

13.9

13.3

12.7

12.2

12.0

11.3

10.7

8.1

7.6

7.2

6.9

6.7

6.1

5.6

5.0

4.4

3.7

 

HI PR

219

210

202

193

189

185

178

171

164

156

150

146

144

138

133

128

123

119

 

LO PR

78

72

67

62

58

56

52

46

42

37

33

30

29

25

21

18

16

12

 

MODEL: GSH13036-3AF/ ARUF49-00*-1* / ARUF36421A*

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

 

MBh

37.2

35.3

33.2

31.0

29.6

28.7

26.7

24.6

23.5

21.7

20.0

18.8

18.1

16.3

14.4

12.6

10.7

8.8

 

Delta T

28.3

26.8

25.2

23.6

22.5

21.8

20.3

18.7

17.9

16.5

15.2

14.3

13.8

12.4

11.0

9.6

8.2

6.7

 

KW

2.64

2.58

2.53

2.47

2.44

2.42

2.36

2.31

2.44

2.38

2.32

2.28

2.26

2.19

2.14

2.08

2.01

1.96

 

AMPS

7.5

7.0

6.6

6.2

6.0

5.9

5.6

5.3

5.1

4.9

4.7

4.6

4.6

4.4

4.1

3.9

3.6

3.3

 

COP

4.13

3.99

3.84

3.67

3.55

3.48

3.30

3.12

2.82

2.67

2.52

2.42

2.35

2.17

1.98

1.77

1.56

1.32

 

EER

14.1

13.6

13.1

12.5

12.1

11.9

11.3

10.7

9.6

9.1

8.6

8.3

8.0

7.4

6.8

6.1

5.3

4.5

 

HI PR

213

204

196

188

183

180

173

166

159

152

146

142

140

134

129

124

120

115

 

LO PR

61

57

53

49

46

44

41

36

33

29

26

24

23

19

17

14

12

10

 

MODEL: GSH13048-3A* / ARUF61-00*-1* / ARUF48601A*

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

 

MBh

54.1

51.2

48.2

45.0

43.0

41.7

38.7

35.7

33.6

31.1

28.6

27.0

26.0

23.3

20.7

18.0

15.4

12.6

 

Delta T

31.3

29.6

27.9

26.1

24.9

24.1

22.4

20.7

19.5

18.0

16.5

15.6

15.0

13.5

12.0

10.4

8.9

7.3

 

KW

3.71

3.64

3.57

3.50

3.45

3.42

3.35

3.28

3.34

3.26

3.19

3.14

3.11

3.04

2.96

2.89

2.81

2.74

 

AMPS

14.6

13.6

12.7

12.0

11.6

11.3

10.7

10.2

9.8

9.3

8.9

8.7

8.6

8.2

7.7

7.2

6.7

6.1

 

COP

4.26

4.11

3.95

3.77

3.64

3.56

3.38

3.18

2.95

2.79

2.63

2.51

2.44

2.25

2.04

1.83

1.60

1.35

 

EER

14.6

14.1

13.5

12.9

12.4

12.2

11.5

10.9

10.1

9.5

9.0

8.6

8.4

7.7

7.0

6.2

5.5

4.6

 

HI PR

224

215

206

197

193

189

182

174

167

159

153

149

147

141

136

130

126

121

 

LO PR

73

68

64

58

55

53

49

44

39

35

31

29

28

23

20

17

15

12

 

MODEL: GSH13060-3A* / ARUF61-00*-1* / ARUF48601A*

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

 

MBh

69.8

66.0

62.2

58.1

55.5

53.8

50.0

46.1

43.6

40.3

37.1

35.0

33.7

30.2

26.8

23.4

20.0

16.3

 

Delta T

35.9

34.0

32.0

29.9

28.5

27.7

25.7

23.7

22.4

20.7

19.1

18.0

17.3

15.6

13.8

12.0

10.3

8.4

 

KW

5.58

5.47

5.35

5.24

5.17

5.12

5.01

4.89

4.37

4.27

4.17

4.11

4.07

3.96

3.86

3.76

3.65

3.55

 

AMPS

22.1

20.4

19.1

18.0

17.3

17.0

16.0

15.2

14.5

13.9

13.2

12.9

12.7

12.1

11.2

10.6

9.8

8.8

 

COP

3.66

3.54

3.40

3.25

3.14

3.07

2.92

2.75

2.92

2.76

2.60

2.49

2.43

2.23

2.03

1.82

1.60

1.35

 

EER

12.5

12.1

11.6

11.1

10.7

10.5

10.0

9.4

10.0

9.4

8.9

8.5

8.3

7.6

6.9

6.2

5.5

4.6

 

HI PR

273

262

252

241

235

231

222

213

204

195

187

182

179

172

166

159

153

148

 

LO PR

72

67

63

58

54

52

48

43

39

35

30

28

27

23

20

17

15

11

*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temperature

High pressure is measured at the suction service valve ( the larger valve). Low pressure is measured at the gauge port connection.

Calculations are based on nominal CFM and 70 °F indoor dry bulb.

AMPS = Outdoor unit amps (comp.+fan) KW = Total system power

23

Image 23
Contents Technical Manual Product Identification 036GSH130484AC Product Design Model Dimensions W x D x H Product DimensionsHeat Pump Specifications Cooling Performance Data 154 29.110.5 10.9 11.3 11.1 11.9GSH130363AF 243 Outdoor Ambient Temperature 105 11531.4 41.7 105 11542.9 12.913.0 44.611.1 11.0 11.2 12.216.7 51.417.0 13.6 14.0 14.514.7 15.2 15.7 15.9 16.5 17.1GSH130484AC 55.8 59.7 63.8 53.4 54.5 58.3 62.3 54.9813.6 14.0 14.5 14.3 14.7 15.2 15.7 160 169 176 167 180 190 198189 GSH130484AD45.9 140 133 143 10.1 10.510.3 10.7 11.0 127233 GSH130604AC10.1 11.3 11.6 12.0 52.8511.2 11.5 11.9 10.8 11.1 11.4GSH130483B 184 177 191 179 172 18557.0 54.3 45.4 46.424.9 Heating Performance DataGSH13048-604AC Diagrams WiringGSH130363AF GSH13048-604AC