Goodmans RT6212008x5, GSH 13 SEER - 3 Phase Split System Heat Pump service manual GSH13048-604AC

Page 24

HEATING PERFORMANCE DATA

 

 

 

GSH130[48-60]4AC

 

 

 

 

 

 

EXPANDED PERFORMANCE DATA

 

 

 

 

 

MODEL: GSH13048-3A* / ARUF61-00*-1* / ARUF48601A*

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

MBh

54.1

51.2

48.2

45.0

43.0

41.7

38.7

35.7

33.6

31.1

28.6

27.0

26.0

23.3

20.7

18.0

15.4

12.6

Delta T

30.6

29.0

27.3

25.5

24.4

23.6

21.9

20.2

19.1

17.6

16.2

15.3

14.7

13.2

11.7

10.2

8.7

7.1

KW

4.11

4.04

3.96

3.88

3.84

3.81

3.73

3.65

4.07

3.98

3.89

3.84

3.80

3.71

3.62

3.53

3.44

3.35

AMPS

8.6

8.1

7.7

7.3

7.1

7.0

6.7

6.4

6.2

6.0

5.8

5.7

5.6

5.4

5.2

5.0

4.7

4.4

COP

3.85

3.71

3.56

3.39

3.28

3.20

3.03

2.86

2.42

2.28

2.15

2.06

2.00

1.84

1.67

1.49

1.31

1.10

EER

13.1

12.7

12.2

11.6

11.2

10.9

10.4

9.8

8.3

7.8

7.3

7.0

6.8

6.3

5.7

5.1

4.5

3.8

HI PR

252

242

232

222

217

213

205

196

188

180

173

168

165

159

153

147

141

136

LO PR

76

71

66

61

57

55

51

45

41

36

32

30

29

24

21

18

15

12

MODEL: GSH13060-3A* / ARUF61-00*-1* / ARUF48601A*

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

MBh

69.8

66.0

62.2

58.1

55.5

53.8

50.0

46.1

43.6

40.3

37.1

35.0

33.7

30.2

26.8

23.4

20.0

16.3

Delta T

34.3

32.5

30.6

28.6

27.3

26.4

24.6

22.7

21.4

19.8

18.2

17.2

16.6

14.9

13.2

11.5

9.8

8.0

KW

5.25

5.15

5.05

4.95

4.89

4.85

4.75

4.65

5.20

5.08

4.96

4.89

4.84

4.72

4.61

4.49

4.37

4.25

AMPS

10.5

9.8

9.3

8.9

8.6

8.5

8.1

7.7

7.5

7.2

7.0

6.8

6.8

6.5

6.2

5.9

5.6

5.2

COP

3.89

3.75

3.60

3.44

3.32

3.25

3.08

2.90

2.46

2.32

2.19

2.09

2.04

1.87

1.70

1.52

1.34

1.12

EER

13.3

12.8

12.3

11.7

11.3

11.1

10.5

9.9

8.4

7.9

7.5

7.2

7.0

6.4

5.8

5.2

4.6

3.8

HI PR

270

258

248

238

232

228

219

210

201

192

184

180

177

170

164

157

151

146

LO PR

77

71

67

61

58

56

51

46

41

37

32

30

29

25

21

18

16

12

*Note: Shaded area is AHRI Rating Conditions at 47° outdoor ambient temperature

 

 

 

 

 

 

 

 

 

MODEL: GSH130483B*, 484A* / AR*F496016B

 

 

 

 

 

 

 

 

HEATING OPERATION

 

 

 

 

 

 

 

Outdoor Ambient Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

60

55

50

47

45

40

35

30

25

20

17

15

10

5

0

-5

-10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MBh

60.1

56.9

53.6

50.1

47.8

46.3

43.0

39.7

35.9

33.1

30.5

28.8

27.7

24.9

22.1

19.2

16.4

13.5

Delta T

34.8

32.9

31.0

29.0

27.7

26.8

24.9

23.0

20.8

19.2

17.7

16.7

16.1

14.4

12.8

11.1

9.5

7.8

KW

4.54

4.43

4.33

4.23

4.17

4.12

4.02

3.92

3.55

3.45

3.35

3.30

3.26

3.16

3.07

2.97

2.87

2.78

AMPS

13.6

12.6

11.8

11.2

10.8

10.6

10.0

9.6

9.2

8.8

8.4

8.2

8.1

7.7

7.3

6.9

6.4

5.8

COP

3.88

3.76

3.62

3.47

3.36

3.29

3.13

2.97

2.96

2.81

2.66

2.56

2.49

2.30

2.11

1.89

1.67

1.42

EER

13.2

12.8

12.4

11.9

11.5

11.2

10.7

10.1

10.1

9.6

9.1

8.7

8.5

7.9

7.2

6.5

5.7

4.8

HI PR

266

255

245

234

229

224

216

207

198

189

182

178

174

168

161

155

149

144

LO PR

77

71

67

61

58

56

51

46

41

37

32

30

29

24

21

18

16

12

High pressure is measured at the suction service valve ( the larger valve).

Low pressure is measured at the gauge port connection.

Calculations are based on nominal CFM and 70 °F indoor dry bulb.

PERFORMANCE TEST

AMPS = Outdoor unit amps (comp.+fan) KW = Total system power

All data based upon listed indoor dry bulb temperature. .00 inches exter- nal static pressure on coil of outdoor section. Indoor air cubic feet per minute (CFM) as listed in the Performance Data Sheets:

If conditions vary from this, results will change as follows:

1.As indoor dry bulb temperatures increase, a slight increase will occur in indoor air temperature drop (Delta T). Low and high side pressures and power will not change.

2.As indoor CFM decreases, a slight increase will occur in indoor temperature drop (Delta T). A slight decrease will occur in low and

high side pressures and power.

24

A properly operating unit should be within plus or minus 2 degrees of the subcooling value shown in the Heat Pump Specifications.

A properly operating unit should be within plus or minus 3 degrees of the typical (Delta T) value shown.

A properly operating unit should be within plus or minus 7 PSIG of the HI PR shown.

A properly operating unit should be within plus or minus 3 PSIG of the LO PR shown.

A properly operating unit should be within plus or minus 3 Amps of the typical value shown.

Image 24
Contents Technical Manual 036 Product IdentificationGSH130484AC Product Design Product Dimensions Model Dimensions W x D x HHeat Pump Specifications Cooling Performance Data 29.1 10.5 10.9 11.3 11.111.9 154GSH130363AF Outdoor Ambient Temperature 105 115 31.4243 105 115 42.912.9 41.744.6 11.1 11.0 11.212.2 13.051.4 16.713.6 14.0 14.5 14.7 15.2 15.715.9 16.5 17.1 17.0GSH130484AC 54.98 13.6 14.0 14.5 14.3 14.7 15.2 15.7160 169 176 167 180 190 198 55.8 59.7 63.8 53.4 54.5 58.3 62.3GSH130484AD 45.9189 10.1 10.5 10.3 10.7 11.0127 140 133 143GSH130604AC 10.1233 52.85 11.2 11.5 11.910.8 11.1 11.4 11.3 11.6 12.0GSH130483B 179 172 185 57.054.3 45.4 46.4 184 177 191Heating Performance Data 24.9GSH13048-604AC Wiring DiagramsGSH130363AF GSH13048-604AC