EMI T3HB, T4HB, T2HB, S2HB manual Defrost Control

Page 21

Single-Zone and Dual-Zone Sequence of Operation

Testing Defrost Operation using test pins

Defrost Control

DFT TST

R and DF2

Warning!

Before removing the access panels to the unit make sure that all power is dis- connected from the unit. Failure to do so could result in injury or electric shock.

Defrost operation can be initiated us- ing the test pins located on the circuit board of the condensing unit. “Defrost test operation” will be a time compressed ver- sion of the actual defrost cycle.

With the system “off”, using two small alligator clips, jumper the following sets of test pins. “R and DF2” and “DFT TST”.

Defrost control board: Apply power to the indoor and outdoor units. Place the indoor unit in heating mode with the set point temperature well above room tem- perature. This is to ensure that the con- denser will remain on during the entire defrost test operation.

The condenser will operate in heat- ing for approximately 20 seconds. At that point the unit will enter defrost mode for approximately 2 seconds. During this time the condenser fan will switch off, the re- versing valve will energize and the defrost board will energize the indoor electric heat relay through the “W” terminal. After

the two second defrost cycle is complete, the unit will switch back to heating opera- tion for another 20 seconds. This process will repeat until the jumpers are removed from the test pins.

Note: If the condenser coil is heavily frosted up with ice, it is likely that the “Defrost Sensor” is already closed. In this case the “R and DFT” jumper can be eliminated. To initiate defrost, mo- mentarily jump pins marked “DFT TST” until the defrost cycle begins. The unit will remain in defrost mode until the condenser coil is defrosted and then it will return to heating mode. When test- ing is complete be sure to remove the jumper(s). DO NOT leave the unit in test mode with jumper(s) in place.

Defrost controls with short cycle protection (heat pumps only): The unit is equipped with a logic control circuit de- signed to keep system operating at peek efficiency. The 24v circuit provides control to the indoor and outdoor systems includ- ing a three minute, anti-short cycle timer (ASCT) compressor protection.

The defrost control circuit is designed to keep the condenser coil free from frost and ice during heating mode. This is ac- complished through the precise switching sequence of the outdoor fan, reversing valve and indoor auxiliary heater.

Defrost initiation: The defrost-sensor is located on either the end plate or the re- turn bend of the condenser coil. A defrost cycle will initiate after the sensor closes (approx. 30° F) and remains closed for the length of time selected on the control board (either 30, 60 or 90 minutes)*.

At the start of the defrost cycle, the re- versing valve will change from heating to cooling mode. The condenser fan will also switch off, there-by allowing pressure and temperature to rise within the condenser

Multi-zone Heat Pump Condensing Units

21

www.enviromaster.com

Image 21
Contents Installation, operation and maintenance Manual EMI America Series Multi-zone Heat Pump Condensing Units To the Installer Safety InstructionsDescription Installer Supplied ItemsSystem Options Items for ConsiderationS2HB Unit Mounting Section S2HB Installation Instructions SectionRating plate S2HB Electrical Wiring Installation SectionCompleted Electrical Connections Low Volt ConnectionElectrical Wiring DiagramWith a screw Driver punch S2HB, T2HB, T3HB, & T4HB models Multi-Zone Heat Pump Refrigerant Piping InstallationTrap may be fabricated using Trap InstallationBraze tubing into fittings Piping Connections Recap of COMPLETingField Charging Multi-zone Heat Pump Field Charging Multi-zone Heat Pump Field Charging Multi-zone Heat Pump Field Charging Multi-zone Heat Pump Field Charging Starting the Unit On the R-22 Scale of the low- side gaugeTest Unit Performance Data Start-up and Troubleshooting Test procedurePump Multi-zone Condenser Sequence of OperationDefrost Control Operation and Maintenance Specific ChangesGeneral Recommendations Specifications may change without notice S2HB dimensions and specificationsHspf S2HB System PerformanceUNH S2HB Liquid Suction T2HB, T3HB, and T4HB dimensions and specificationsT2HB, T3HB, & T4HB models T2HB, T3HB, and T4HB specificationsT2HB, T3HB, or T4HB Top Discharge CAH T3HB, or T4HB EMI’s High Seer Product Line Phone Success Drive Fax Rome, NY

S2HB, T2HB, T3HB, T4HB specifications

The EMI T4HB, T3HB, T2HB, and S2HB models represent innovative advancements in the field of electronic security and surveillance technology. Each model is designed to meet specific security needs while integrating cutting-edge features, making them suitable for a variety of applications, from residential monitoring to large-scale facility management.

Starting with the T4HB, this model is known for its high-definition video capabilities and robust build quality. It offers 4K resolution, providing crystal-clear image quality that captures fine details, making it easier to identify subjects. The T4HB is equipped with advanced night vision technology, allowing it to perform optimally in low light conditions. Additionally, it features motion detection and smart analytics that minimize false alarms and provide users with real-time alerts. The integration with cloud storage solutions ensures that footage is securely saved and easily accessible from various devices.

The T3HB is a slightly scaled-back version, yet it does not compromise on essential features. It supports 1080p full HD resolution and incorporates many of the same intelligent analytics capabilities as its T4HB counterpart. With a wide-angle lens, the T3HB allows coverage of larger areas with fewer cameras. Its weather-resistant design makes it suitable for both indoor and outdoor installations, protecting it from the elements and ensuring reliable performance.

Next is the T2HB, which balances performance and affordability. This model retains high-definition video quality and basic motion detection features, making it ideal for budget-conscious consumers who still want reliable surveillance. The T2HB focuses on user-friendliness with simple setup processes and mobile app integration that allows for easy remote monitoring, making it an attractive option for homeowners.

Lastly, the S2HB is engineered for versatility. It combines the advantages of all previous models, providing excellent video quality and configurable settings for personalized security needs. The S2HB stands out with its smart home compatibility, enabling integration with various smart devices in a home security ecosystem. Its compact design allows for flexible mounting options without compromising performance.

Together, the EMI T4HB, T3HB, T2HB, and S2HB models reflect a commitment to quality, innovation, and user satisfaction in the modern security landscape. They cater to various needs, ensuring that users can find a suitable solution for their surveillance requirements while benefiting from advanced technologies that enhance security and peace of mind.