Bard PA13302-A Wiring Main Power, Wiring 24V LOW Voltage Control Circuit, Transformer Taps

Page 14

WIRING – MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. If field installed heaters are added to the basic unit, a second separate power supply circuit will be required. The heater rating plate located adjacent to the basic unit rating plate will show the appropriate circuit ampacity fuse size, etc. (Also see “Electrical Specifications” on pages 5 & 7.) All models are suitable for connection with copper wire only. These instructions must be adhered to. Refer to the National Electrical Code for complete current carrying capacity data on the various insulation grades of wiring material.

The electrical specifications list fuse and wire sizes (75°F copper) for all models including the most commonly used heater sizes.

The unit rating plate lists a “Maximum Time Delay Fuse” or “HACR” type circuit breaker that is to be used with the equipment. The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting current of the compressor.

WIRING – 24V LOW VOLTAGE CONTROL CIRCUIT

Five (5) wires should be run from thermostat subbase to the 24V terminal board in the unit. A five conductor, 18 gauge copper, color-coded thermostat cable is recommended. The connection points are shown in Figure 6.

TABLE 6

THERMOSTAT WIRE SIZE

Transformer

 

Wire

Maximum

FLA

Distance

VA

Gauge

 

In Feet

 

 

 

 

 

20

45

 

 

18

60

55

2.3

16

100

 

 

14

160

 

 

12

250

TRANSFORMER TAPS

230/208V, 1 phase and 3 phase equipment employ dual primary voltage transformers. All equipment leaves the factory wired on 240V tap. For 208V operation, reconnect from 240V to 208V tap. The acceptable operating voltage range for the 240 and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

NOTE: The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load (maximum amperage operating condition).

THERMOSTATS

See specific wiring information for the different models, heater KWs, and voltages on unit and heating wiring diagrams.

 

 

TABLE 7

 

WALL THERMOSTATS

 

 

 

Thermostat

 

Predominant Features

8403-058

 

2 stage Cool; 2 stage Heat

 

Electronic Non-Programmable

(TH5220D1151)

 

 

Auto or Manual changeover

 

 

 

 

3 stage Cool; 3 stage Heat

8403-060

 

Programmable/Non-Programmable Electronic

(1120-445)

 

HP or Conventional

 

 

Auto or Manual changeover

IMPORTANT NOTE: Only the thermostats as shown above will work with this equipment. The thermostats and correct operation can be assured only by proper selection and application of these parts.

Manual

2100-467K

Page

14 of 24

Image 14
Contents Installation Instructions Single Package AIR Conditioners Contents Getting Other Information and Publications For more information, contact these publishersShipping Damage Field Installed Heater Packages OptionalGeneral Instructions GeneralElectrical specifications Hz Circuit a2100-467K Optional Field Installed Electric Heater Table BtuhUnit Dimension Chart Dimensions of UnitsUnit Location InstallationTypical Installations GeneralAirflow and Service access clearances Slab Mounting at Ground levelElevated mounting platform As requiredFilter requirements & Sizes Condensate Drain TrapAIR Filters Condensate Drain TrapTransformer Taps Wiring Main PowerWiring 24V LOW Voltage Control Circuit ThermostatsLow Voltage Wiring LOW Voltage WiringTopping off system charge Safety practicesStart UP Start UP NotesSequence of Operation Three Phase Scroll Compressor STart UP InformationStart UP and Operation INDOOR Blower MotorAdjustable DELAY-ON-MAKE and DELAY-ON-BREAK Timer AdjustmentsAlarm Output LOW ambient controlPressure Service Ports Service and TroubleshootingService Hints FAN Blade SettingsPressure Table On Page 20 in Table126 128 129 Brazing Diagram Suction and Discharge Tube BrazingTroubleshooting GE X13-Series ECM2.3 Motors Troubleshooting GE X13-Series ECM2.3 Motors Cont’d

PA13422-A, PA13482-C, PA13362-A, PA13242-A, PA13602-B specifications

The Bard PA13362-B, PA13482-B, PA13482-A, PA13422-C, and PA13422-B are advanced heating and cooling systems designed to meet the diverse needs of residential and commercial settings. These models are well-regarded for their innovative technologies, efficiency, and reliability.

At the heart of these units is Bard's commitment to superior engineering. The PA13362-B and PA13482-B, for instance, are equipped with powerful compressors that deliver exceptional cooling performance while maintaining energy efficiency. Both models utilize a high-efficiency refrigerant which not only complies with environmental regulations but also enhances their cooling capabilities. Their robust construction ensures durability and longevity, making them a smart investment for users looking for long-term solutions.

The PA13482-A and PA13422-C models are noteworthy for their advanced airflow design, which ensures consistent temperature distribution throughout the space. This is especially beneficial in large areas where temperature fluctuations can be a concern. The designs are optimized to minimize noise levels, providing a tranquil environment without compromising on performance.

Energy efficiency is a hallmark feature across these models. Many units incorporate variable-speed technology, which allows them to adjust their operation based on the specific heating or cooling needs of the environment. This not only reduces energy consumption but also leads to lower utility bills over time. Furthermore, the units are designed with easy maintenance features, enabling users to perform routine checks with minimal effort.

The PA13422-B model stands out with its programmable control options, which allow for customized heating and cooling schedules. This feature is particularly advantageous for businesses and households looking to optimize their energy usage and occupancy comfort. The intuitive interface is user-friendly, ensuring quick access to settings and adjustments.

Overall, Bard's PA series units offer a combination of high performance, efficiency, and user-friendly features. They are suitable for various applications, enhancing comfort in schools, offices, and homes alike. With a focus on innovation and customer satisfaction, Bard continues to set the standard in heating and cooling technology, making their models some of the most reliable choices in the market today.