Bard P1124A3, P1224A2 installation instructions Location, Typical Installations

Page 11

INSTALLATION

LOCATION

GENERAL

The unit must be located outside, or in a well ventilated area. It must not be in the space being heated or cooled. A sound absorbing material should be considered if the unit is to be installed in such a position or location that might cause transmission of sound or vibration to the living area or adjacent buildings.

SLAB MOUNTING

In areas where winter temperatures DO NOT go below 32° F for periods over twelve hours, the unit may be slab mounted at grade level. When installing unit at grade level, install on a concrete slab at least four inches above finished grade level. Slab should have a slope tolerance away from the building structure of at lease 1/4 inch per foot, while being level from side to side. Place slab in a location where runoff water from higher ground will not collect around unit. See Figure 2.

A minimum of 18 inches should be provided between the coil inlet and any building surfaces. Provide at least four feet between coil outlet and any building wall, fences or other vertical structures. Provide a minimum of three feet clearance on the service access side of the unit. See Figure 3.

ROOF MOUNTING

When a unit is installed in areas where low ambient temperatures or strong winter winds exist, it should be placed for prevailing winter winds are not in direct line with the outdoor coil. If this is not possible, a wind barrier should be constructed. Place barrier 24 inches from the coil inlet side of the unit and in the direction of prevailing winds. Size barrier at least the same height and width as the unit. This may be necessary on ground level installations, also. See Figure 4.

WINTER INSTALLATION BELOW 32°F

In areas where winter conditions go below 32°F for extended periods, the unit must be elevated above the mounting surface to prevent snowfall or ice accumulation from interfering with the operation of the unit. A minimum of twelve inch elevation is recommended, while greater elevation may be required for areas of high snow accumulation. Poured concrete, steel framework, brick, cement block, etc., can be utilized to construct a suitable raised mounting platform. See Figure 5.

TYPICAL INSTALLATIONS

1.ROOF MOUNTED – The unit is mounted on a sturdy base on the roof of the building. Return air to the unit is brought through a single return grille (grilles with built-in filters are best since they enable easy access for filter changing). Return air ducts are attached to the lower section of the front panel. Supply air is brought from the unit to attic duct work or to a furred down hall. Supply air duct is attached to the top of the front panel.

CAUTION: All outdoor duct work must be thoroughly insulated and weatherproofed. All attic duct work must be thoroughly insulated. Two inch thick insulation with suitable vapor barrier is recommended for both outdoor and attic runs.

In roof top installation, as in all installations, the air conditioner must be level from side to side. However, the unit should have a pitch along the length to assure complete external drainage of precipitation and of defrost condensate. See Figures 6 and 7, and Tables 6 and 7.

2.CRAWL SPACE – Duct work installed in crawl space must be well insulated and provided with a vapor barrier. In addition, the crawl space must be thoroughly ventilated and provided with a good vapor barrier as a ground cover. It is most desirable to install the unit will be outdoors rather than inside the crawl space, so that it will be readily accessible for service.

3.SLAB MOUNTED AT GROUND LEVEL – This type installation is ideal for homes with a slab floor construction where a roof mounted unit is not desired. The supply and return duct work can be run through a furred closet space.

4.THROUGH THE WALL – This type installation requires a suitable framework to be fabricated capable of withstanding the unit weight. Normally the unit will be insulated so as to minimize supply and return duct work.

Manual 2100-353 Page 9

Image 11
Contents Installation Instructions Single Package AIR Conditioners Contents For More INFORMATION, Contact These Publishers Getting Other Information and PublicationsGeneral Field Installed Heater Packages OptionalGeneral Instructions Shipping DamageFan Motor and Condenser Electrical SpecificationsHz Circuit a Compressor Circuit a414 Fan Motor and Condenser Intentionally Heater Package Volts Model PhaseThis column Is left blankSize Optional Field Installed Electric Heater TableHtr. KW Circuit B Capacity @ 240 Volts @ 208 Volts Htr. Amps Fuses Circuits Ampacity ProtectionDimensions of Units Location InstallationTypical Installations Slab Mounting AT Ground Level Airflow and Service Access ClearancesElevated Mounting Platforms Roof TOP ApplicationMIS-1177C Field Fabricated Curbing Dimension for X in FIGUnit Model Roof Hood Dimension Roof Curb DetailsCondensate Drain Trap Condensate Drain TrapAIR Filters Filter Requirements & SizesThermostats Wiring Main PowerWiring 24V LOW Voltage Control Circuit Transformer TapsLOW Voltage Wiring Start UP and Operation Adjustable DELAY-ON-MAKE and DELAY-ON-BREAK Timer AdjustmentsLOW Pressure SWITCH, BYPASS, and Lockout Sequence Alarm OutputFAN Blade Settings Service and TroubleshootingService Hints Pressure Service PortsESP P1124A3 P1130A2 P1136A2 P1142A3 P1148A2 P1060A1 Brazing DiagramSuction and Discharge Tube Brazing Indoor Blower PerfomanceReturn Air Pressure 100 105 110 115 Model Pressure TablePressure Table Evidence of Moisture Troubleshooting ECM Blower MotorsMotor rocks slightly when starting Motor wont start ∃ Run Mositure Check∃ Perform Moisture Check Motor starts but runs erraticallyExcessive noise Page Page Page Page Page Page Page

P1124A3, P1224A2 specifications

The Bard P1224A2 and P1124A3 are advanced heating solutions designed to meet the demanding needs of commercial and residential spaces. These models reflect Bard's commitment to quality, efficiency, and innovation in the HVAC (Heating, Ventilation, and Air Conditioning) industry.

At the heart of the Bard P1224A2 and P1124A3 is their robust design, engineered for durability and long-lasting performance. The P1224A2 model is specifically tailored for applications requiring efficient heating and cooling across diverse environmental conditions. It boasts an exceptional heating capacity, making it suitable for moderate to large spaces, while also providing reliable climate control during the warmer months. The P1124A3, on the other hand, focuses on energy efficiency and versatility, making it an ideal choice for various settings including schools, offices, and healthcare facilities.

Both models utilize advanced technologies that enhance their operational efficiency. They incorporate high-performance compressors designed to optimize energy consumption without sacrificing output. The energy-efficient design of these units not only lowers operational costs but also contributes to reducing the overall carbon footprint, making them environmentally friendly options.

In terms of features, the Bard P1224A2 and P1124A3 are equipped with state-of-the-art controls that enable users to easily adjust settings for maximum comfort. The intuitive interface allows for precise temperature adjustments and scheduling options, ensuring a consistent and pleasant indoor environment. Additionally, these units are compatible with smart building systems, which can be integrated for remote monitoring and control.

Noise reduction technology is another key characteristic of these models. Their design minimizes operational noise, which is crucial for environments where sound levels are critical, such as educational institutions and medical facilities.

Lastly, both the P1224A2 and P1124A3 feature a compact footprint, ensuring flexible installation options even in tight spaces. Their rugged construction is built to withstand harsh weather conditions, providing peace of mind and reliability year-round.

In conclusion, the Bard P1224A2 and P1124A3 stand out in the HVAC market due to their exceptional efficiency, advanced technology, and user-friendly features. They represent a solid investment for anyone looking to improve climate control in their buildings while also prioritizing sustainability and cost-effectiveness.