Bard P1224A2, P1124A3 installation instructions 414

Page 6

TABLE 2A

ELECTRICAL SPECIFICATIONS

Model

P1148A2

P1148A2-B

P1148A2-C

P1060A1

P1060A1-B

P1060A1-C

 

 

 

 

 

 

 

Electric Rating –

230/208-60-1

230/208-60-3

460-60-3

230/208-60-1

460-60-3

460-60-3

60 Hz – Circuit A

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating Voltage Range

197 - 253

187 - 253

414 - 506

197 - 253

187 - 253

414 - 506

Minimum Circuit Ampacity

32

24

12

42

28

14

 

 

 

 

 

 

 

BCSC

20.5

14.7

7

29

12

9

Field Wire Size *

8

10

12

8

8

12

 

 

 

 

 

 

 

Ground Wire Size

10

10

12

10

10

12

Delay Fuse – Max. **

50

35

15

60

45

20

 

 

 

 

 

 

 

Tota unit Amps – 230/208

24.2/26.2

17.9/19.1

8.8

30.9/33.7

21.7/23.7

11.2

Compressor – Circuit A

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor Type

Scroll

Scroll

Scroll

Scroll

Scroll

Scroll

Volts

230/208

230/208

460

230/208

230/208

460

 

 

 

 

 

 

 

Rated Load Amps

18.5/20.5

12.2/13.4

6

25.2/28.2

16/18

8.4

Lock Roter Amps

137/137

91/91

50

169/169

123/123

62

 

 

 

 

 

 

 

Fan Motor and Condenser

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan Motor – HP/RPM

1/3 - 850

1/3 - 850

1/3 - 850

1/3 - 850

1/3 - 850

1/3 - 850

 

 

 

 

 

 

 

Fan Motor Amps

2.5

2.5

1.2

2.5

2.5

1.2

 

 

 

 

 

 

 

Fan – Dia./CFM

24"/3100

24"/3100

24"/3100

24"/3100

24"/3100

24"/3100

 

 

 

 

 

 

 

Motor and Evaporator

 

 

 

 

 

 

 

 

 

 

 

 

 

Blower Motor – HP/RPM

1/2 - 1075

1/2 - 1075

1/2 - 1075

1/2 - 1075

1/2 - 1075

1/2 - 1075

Blower Motor – Amps

3.2

3.2

1.6

3.2

3.2

1.6

 

 

 

 

 

 

 

CFM Cooling & ESP

1550 @ 0.40

1550 @ 0.40

1550 @ 0.40

1700 @ 0.20

1700 @ 0.20

1700 @ 0.20

Charge (R22 oz.)

 

 

 

120

120

120

 

 

 

 

 

 

 

Shipping Weight (pounds)

430

430

430

425

425

425

Manual 2100-353 Page 4

Image 6
Contents Installation Instructions Single Package AIR Conditioners Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersShipping Damage Field Installed Heater Packages OptionalGeneral Instructions GeneralCompressor Circuit a Electrical SpecificationsHz Circuit a Fan Motor and Condenser414 Fan Motor and Condenser Is left blank Heater Package Volts Model PhaseThis column IntentionallyHtr. Amps Fuses Circuits Ampacity Protection Optional Field Installed Electric Heater TableHtr. KW Circuit B Capacity @ 240 Volts @ 208 Volts SizeDimensions of Units Installation Typical InstallationsLocation Airflow and Service Access Clearances Slab Mounting AT Ground LevelRoof TOP Application Elevated Mounting PlatformsMIS-1177C Roof Curb Details Dimension for X in FIGUnit Model Roof Hood Dimension Field Fabricated CurbingFilter Requirements & Sizes Condensate Drain TrapAIR Filters Condensate Drain TrapTransformer Taps Wiring Main PowerWiring 24V LOW Voltage Control Circuit ThermostatsLOW Voltage Wiring Start UP and Operation Alarm Output AdjustmentsLOW Pressure SWITCH, BYPASS, and Lockout Sequence Adjustable DELAY-ON-MAKE and DELAY-ON-BREAK TimerPressure Service Ports Service and TroubleshootingService Hints FAN Blade SettingsIndoor Blower Perfomance Brazing DiagramSuction and Discharge Tube Brazing ESP P1124A3 P1130A2 P1136A2 P1142A3 P1148A2 P1060A1Pressure Table Return Air Pressure 100 105 110 115 ModelPressure Table ∃ Run Mositure Check Troubleshooting ECM Blower MotorsMotor rocks slightly when starting Motor wont start Evidence of MoistureMotor starts but runs erratically Excessive noise∃ Perform Moisture Check Page Page Page Page Page Page Page