Bard HAC181-AD040 Optional Controls, Installation Instructions CMA-5, Component Mounting Location

Page 14

OPTIONAL CONTROLS

FIGURE 5

COMPONENT MOUNTING LOCATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CMA-5 & CMA-13A LOW

CMA-5 COMPRESSOR

AMBIENT FAN CYCLING

TIME DELAY RELAY

CONTROL

TERMINAL BLOCK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SK109 LOW VOLTAGE

CMA-10A & CMA-13A

START KIT

COMPRESSOR

 

 

CONTROL

MIS-1302

INSTALLATION INSTRUCTIONS — CMA-5

Disconnect all power to the unit. Remove control panel cover.

1.Mount compressor TDR in position shown in Figure 5 with screw provided.

2.Disconnect yellow low voltage (Y) wire at the compressor contactor coil and reconnect to the Y1 or #3 terminal of the TDR.

3.Connect yellow wire from terminal (Y) of the TDR to the (Y) terminal of the compressor contactor coil. This is the terminal that the wire was removed from in Step 2.

4.Recheck wiring. Refer to Figure 9. Energize unit. Compressor should start. Remove power and reapply. Compressor should not start until the 5 minute time delay has expired.

5.Apply “This unit equipped with CMA-5 control module” label to inside of the inner control panel cover above wiring diagram.

6.Replace all panels and covers. This completes installation.

FIGURE 6

INSTALLATION INSTRUCTIONS

FOR CMA-5 COMPRESSOR TIME DELAY RELAY

MIS-598

INSTALLATION INSTRUCTIONS — CMA-6

Disconnect all power to unit. Remove control panel inner and outer cover.

1.Mount terminal block in position shown in Figure 5.

2.Disconnect black high voltage outdoor motor lead from compressor contactor and reconnect to terminal block.

3.Route low ambient control wires up through the bushing in the bottom of the control panel. Connect the low ambient control wires between the terminal block and T2 of the compressor contactor.

4.Remove service port cap on discharge line. Install the low ambient control on the discharge line with the flare tee adapter that is brazed to the low ambient control. Check for pressure at the flare tee dill valve after installation to insure that the dill valve in the unit service port was depressed by the flare tee connector. Check for leaks at the flare tee connectors. Replace service port cap on the flare tee service port and tighten.

5.Recheck wiring. See Figure 10. Check for proper operation of the unit by energizing in cooling mode. The condenser fan motor should not run until the discharge pressure has exceeded 300 PSI. Should the discharge pressure fall below 200 PSI while running, the condenser fan motor will de-energize until the head pressure builds to 300 PSI.

6.Apply “This unit equipped with CMA-6 control module” label to the inside of the control panel cover above the wiring diagrams.

7.Replace all panels and covers. This completes installation.

FIGURE 7

INSTALLATION INSTRUCTIONS FOR

CMA-6 LOW AMBIENT FAN CYCLING CONTROL

MIS-594

Manual 2100-346 Page 12

Image 14
Contents Bard Manufacturing Company Contents Split AIR Conditioner Model Nomenclature Unit Dimensional DrawingUnit Dimensions Rated CFM and AIR Flow Data WET Coil Cooling CFMSpecifications ModelsGeneral Important Installer NoteInstallation Refrigerant Tubing Shipping DamageInstalling Refrigerant Tubing Flow Control Assembly Field Orifice Replacement InstructionsTubing Chart Manual 2100-346 Couplings Control Diagrams Control Circuit WiringControl Circuit Wiring Wall ThermostatsManual 2100-346 Manual 2100-346 Optional Controls Installation Instructions CMA-5Installation Instructions CMA-6 Component Mounting LocationCompressor Time Delay Relay Installation Instructions CMA-10AInstallation Instructions for Installation Instructions CMA-13A System START-UP Indoor Units Without Expansion Valves Pressure Service PortsSaturated Suction Temperature R-22 System SuperheatTotal System Operating Charge Schedule for TableFAN Blade Setting Service HintsFAN Blade Setting Dimensions FAN BladeManual 2100-346 Manual 2100-346 Pressure Table HAC181-AHAC301-A HAC 421-A HAC601-A HAC601-B

HAC601-BD040, HAC481-BD040, HAC181-AD040, HAC361-AD040, HAC481-AD040 specifications

The Bard HAC series, specifically the HAC421-AD040, HAC241-AD040, HAC301-AD040, HAC601-AD040, and HAC481-AD040 models, represents a versatile and robust selection of commercial heating and cooling systems designed for a variety of applications. These units are known for their efficiency, reliability, and innovative features, making them ideal for business, industrial, and institutional use.

One of the standout characteristics of the Bard HAC series is its energy efficiency. Each model is built to operate at high efficiency levels, which helps to reduce energy costs and contributes positively to environmental sustainability. The units typically feature advanced technology such as dual-fuel operation, allowing them to run on electricity and gas, providing flexibility in cost management depending on energy prices.

The HVAC systems are designed with the user experience in mind, incorporating easy-to-use digital controls. These controls provide users with the ability to adjust settings precisely and monitor system performance easily, contributing to improved comfort levels in any space. Additionally, the HAC series is known for its quiet operation, reducing noise pollution and creating a serene environment conducive to productivity.

Durability is another key aspect of the Bard HAC series. Built with high-quality materials, these units are designed to withstand the rigors of commercial use. Protective coatings and robust construction make them suitable for various applications, from schools and hospitals to warehouses and retail spaces.

Another important feature is their compact design, which allows for easy installation in tight spaces. This attribute is particularly valuable for urban environments where space is at a premium. The units also have a range of customizable options, including various sizes and heating and cooling capacities, ensuring that they can meet specific operational needs.

Bard HVAC also places an emphasis on ease of maintenance. With easily accessible components and straightforward design, routine upkeep can be performed quickly, minimizing downtime and reducing operational costs.

In conclusion, the Bard HAC421-AD040, HAC241-AD040, HAC301-AD040, HAC601-AD040, and HAC481-AD040 models are exemplary choices for those seeking a dependable, efficient, and adaptable heating and cooling solution. With their energy efficiency, user-friendly technology, durability, space-saving designs, and ease of maintenance, these units stand out as leading options for commercial HVAC needs.