TABLE 15
PRESSURE TABLE
HAC301-A
Indoor | Return Air |
|
|
| Air Temperature Entering Outdoor Coil |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 |
| 105 | 110 | 115 | ||
Section | Temp. | Pressure |
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 75 DB | Low Side | 62 | 65 | 67 | 69 | 71 | 73 | 75 | 77 |
| 78 | 80 | 81 |
| 62 WB | High Side | 162 | 183 | 204 | 224 | 244 | 262 | 280 | 297 |
| 313 | 329 | 344 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
80 DB | Low Side | 68 | 70 | 72 | 74 | 76 | 78 | 80 | 82 |
| 84 | 85 | 87 | |
| 67 WB | High Side | 167 | 188 | 210 | 230 | 250 | 269 | 287 | 305 |
| 321 | 338 | 353 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 85 DB | Low Side | 75 | 77 | 78 | 80 | 82 | 84 | 86 | 88 |
| 90 | 92 | 94 |
| 72 WB | High Side | 171 | 194 | 216 | 238 | 258 | 278 | 297 | 315 |
| 333 | 349 | 365 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 75 DB | Low Side | 61 | 65 | 69 | 72 | 75 | 77 | 79 | 81 |
| 82 | 83 | 84 |
| 62 WB | High Side | 185 | 201 | 217 | 234 | 250 | 266 | 282 | 298 |
| 314 | 331 | 347 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
BC36B | 80 DB | Low Side | 67 | 71 | 74 | 77 | 80 | 82 | 84 | 86 |
| 87 | 88 | 89 |
67 WB | High Side | 190 | 207 | 223 | 239 | 256 | 272 | 289 | 306 |
| 322 | 339 | 356 | |
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 85 DB | Low Side | 74 | 77 | 80 | 83 | 86 | 88 | 90 | 92 |
| 93 | 95 | 96 |
| 72 WB | High Side | 198 | 215 | 232 | 248 | 265 | 282 | 299 | 316 |
| 333 | 351 | 368 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low side pressure ± 2 PSIG (suction line 8 inches from compressor)
High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately
Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.
TABLE 16
PRESSURE TABLE
HAC361-A
Indoor | Return Air |
|
|
| Air Temperature Entering Outdoor Coil |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| ||
| 65 | 70 | 75 | 80 | 85 | 90 | 95 | 100 |
| 105 | 110 | 115 | ||
Section | Temp. | Pressure |
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 75 DB | Low Side | 66 | 68 | 70 | 72 | 74 | 76 | 78 | 80 |
| 82 | 84 | 86 |
| 62 WB | High Side | 181 | 197 | 213 | 230 | 246 | 262 | 278 | 294 |
| 310 | 326 | 343 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
80 DB | Low Side | 71 | 73 | 75 | 77 | 79 | 81 | 83 | 85 |
| 87 | 89 | 91 | |
| 67 WB | High Side | 186 | 202 | 219 | 235 | 252 | 268 | 285 | 302 |
| 318 | 335 | 351 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 85 DB | Low Side | 77 | 79 | 81 | 83 | 85 | 87 | 89 | 91 |
| 93 | 95 | 97 |
| 72 WB | High Side | 191 | 208 | 226 | 243 | 260 | 278 | 295 | 312 |
| 330 | 347 | 364 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 75 DB | Low Side | 63 | 66 | 68 | 70 | 72 | 74 | 76 | 78 |
| 79 | 81 | 82 |
| 62 WB | High Side | 178 | 195 | 212 | 228 | 245 | 262 | 279 | 296 |
| 313 | 331 | 348 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
BC36B | 80 DB | Low Side | 66 | 69 | 72 | 75 | 78 | 80 | 82 | 84 |
| 85 | 87 | 88 |
67 WB | High Side | 184 | 200 | 217 | 234 | 251 | 269 | 286 | 304 |
| 321 | 339 | 357 | |
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 85 DB | Low Side | 72 | 75 | 78 | 81 | 83 | 86 | 88 | 90 |
| 92 | 94 | 95 |
| 72 WB | High Side | 188 | 206 | 224 | 242 | 260 | 278 | 296 | 314 |
| 332 | 351 | 369 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Low side pressure ± 2 PSIG (suction line 8 inches from compressor)
High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately
Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.