Bard HAC421-AD040, HAC601-AD040, HAC481-BD040 Total System Operating Charge, Schedule for Table

Page 18

TABLE 11

TOTAL SYSTEM OPERATING CHARGE

(Includes charge for the basic outdoor unit, indoor coil and 25’ of interconnecting tubing.)

 

 

Total R-22

Outdoor Section

Indoor Section

Charge (Oz.)

 

 

 

 

 

A30AS-A

73 oz.

 

HAC181-A

S24AS-A

73 oz.

Q

 

BC24B

78 oz.

 

 

 

 

 

 

A30AS-A

80 oz.

 

HAC241-A

S24AS-A

80 oz.

R

 

BC24B

79 oz.

 

 

 

 

 

HAC301-A

A36AS-A

84 oz.

R

BC36B

95 oz.

 

 

 

 

 

 

 

HAC361-A

A37AS-A

98 oz.

R

BC36B

96 oz.

 

 

 

 

 

 

 

 

A42AS-A

102 oz.

 

HAC421-A

A48AS-A

117 oz. R

BC36B

105 oz.

 

 

 

 

BC60B

142 oz.

 

 

 

 

HAC481-A, -B

A61AS-A

155 oz. R

BC60B

175 oz.

 

 

 

 

 

 

HAC601-A, -B

A61AS-A

153 oz. R

BC60B

165 oz.

 

 

 

 

 

 

 

QIncludes 25’ of 1/4” diameter liquid line. For other than 25’ and other tube sizes, adjust the total charge according to the following schedule.

RIncludes 25’ of 3/8” diameter liquid line. For other than 25’ and other tube sizes, adjust the total charge according to the following schedule.

SCHEDULE FOR TABLE 11

Liquid Line Diameter

Oz. R-22 Per Ft.

 

 

1/4"

0.25

3/8"

0.60

1/2"

1.20

 

 

Installer Note: Stamp or mark the final system charge determined above on the outdoor unit serial plate.

Manual 2100-346 Page 16

Image 18
Contents Bard Manufacturing Company Contents Unit Dimensional Drawing Unit DimensionsSplit AIR Conditioner Model Nomenclature Rated CFM and AIR Flow Data WET Coil Cooling CFMSpecifications ModelsGeneral Important Installer NoteInstallation Refrigerant Tubing Shipping DamageInstalling Refrigerant Tubing Flow Control Assembly Field Orifice Replacement InstructionsTubing Chart Manual 2100-346 Couplings Control Diagrams Control Circuit WiringControl Circuit Wiring Wall ThermostatsManual 2100-346 Manual 2100-346 Optional Controls Installation Instructions CMA-5Installation Instructions CMA-6 Component Mounting Location Installation Instructions CMA-10A Installation Instructions for Compressor Time Delay Relay Installation Instructions CMA-13A System START-UP Indoor Units Without Expansion Valves Pressure Service PortsSaturated Suction Temperature R-22 System SuperheatTotal System Operating Charge Schedule for TableFAN Blade Setting Service HintsFAN Blade Setting Dimensions FAN BladeManual 2100-346 Manual 2100-346 Pressure Table HAC181-AHAC301-A HAC 421-A HAC601-A HAC601-B