TABLE 11
TOTAL SYSTEM OPERATING CHARGE
(Includes charge for the basic outdoor unit, indoor coil and 25’ of interconnecting tubing.)
|
| Total | |
Outdoor Section | Indoor Section | Charge (Oz.) | |
|
|
|
|
| 73 oz. |
| |
73 oz. | Q | ||
| BC24B | 78 oz. |
|
|
|
|
|
| 80 oz. |
| |
80 oz. | R | ||
| BC24B | 79 oz. |
|
|
|
|
|
84 oz. | R | ||
BC36B | 95 oz. |
| |
|
| ||
|
|
|
|
98 oz. | R | ||
BC36B | 96 oz. |
| |
|
| ||
|
|
|
|
| 102 oz. |
| |
117 oz. R | |||
BC36B | 105 oz. |
| |
|
| ||
| BC60B | 142 oz. |
|
|
|
| |
155 oz. R | |||
BC60B | 175 oz. |
| |
|
| ||
|
|
| |
153 oz. R | |||
BC60B | 165 oz. |
| |
|
| ||
|
|
|
|
QIncludes 25’ of 1/4” diameter liquid line. For other than 25’ and other tube sizes, adjust the total charge according to the following schedule.
RIncludes 25’ of 3/8” diameter liquid line. For other than 25’ and other tube sizes, adjust the total charge according to the following schedule.
SCHEDULE FOR TABLE 11
Liquid Line Diameter | Oz. |
|
|
1/4" | 0.25 |
3/8" | 0.60 |
1/2" | 1.20 |
|
|
Installer Note: Stamp or mark the final system charge determined above on the outdoor unit serial plate.