CN8240 & CN8260 Series Communications & Options
Digital
Communications Option
Request Data Fields: | A | |
| specifying what to calibrate. | |
| 0 | - Thermocouple |
| 1 | - RTD, Resistive Thermal Device |
| 2 | - Linear |
| 3 | - RAS, Remote Analog Setpoint |
Response Data Field: | Ignored. | |
Command: | Perform Process High Calibration | |
Parameter #: | 03 | |
Description: | Performs a High Calibration. The data field in the request | |
| message specifies the process. Make sure the prerequisite | |
| for the calibration is satisfied before issuing a calibration | |
| command. For instance, the RTD calibration command must | |
| only be used when the input sensor type is chosen as RTD | |
| or RTD w/ Decimal. | |
Request Data Field: | A | |
| specifying what to calibrate. | |
| 0 | - Thermocouple |
| 1 | - RTD, Resistive Thermal Device |
| 2 | - Linear |
| 3 | - RAS, Remote Analog Setpoint |
Command: | Retrieve Display | |
Parameter #: | 05 | |
Description: | Retrieves the string currently displayed on the slave’s display. | |
| The data field in the request message specifies which display | |
| and the data field in the response message contains the string. | |
Request Data Field: | A 10 character ASCII representation of a numeric value | |
| specifying which display to retrieve data from. | |
| 0 | - Lower Display |
| 1 | - Upper Display |
Response Data Field: | The ASCII string. | |
Command: | Clear Latched Alarms | |
Parameter #: | 10 | |
Description: | Clear all latched alarms. | |
Request Data Field: | Ignored. | |
Response Data Field: | Ignored. |