Omega Engineering CN8260 Option -AL1, -AL2 Relay, N.O. Alarm Output, Load Type Voltage Limit

Page 4

CN8240 & CN8260 Series Communications & Options

Relay, N.O.

Alarm Output

Option -AL1, -AL2: Relay, N.O. Alarm Output

Supply voltage*

Supply voltage*

 

+

N.O.

2

12

 

 

 

 

C

3

13

 

OUTPUT 2

 

 

 

 

+

N.O.

4

14

Load

5 amp fuse

N.O.

5

15

 

ALARM 1

 

 

 

 

 

C

6

16

Load

5 amp fuse

N.O.

7

17

 

ALARM 2

 

 

 

 

 

C

8

18

 

120-250 V

L1

9 21

2219

 

50-60 Hz

L2

1

2

 

 

 

 

0

0

 

 

 

Option Description: NO (Normally open) relay contact is closed when either alarm is active. The relay life is greater than 100,000 operations at 5 operations per second switching full load.

*Connect load and supply voltage per the following table:

Load Type

5 A Voltage Limit

Resistive dc

30 Vdc

 

 

Inductive ac (L/R = 7 ms)

20 Vdc

 

 

Resistive ac

250 Vac

Inductive ac (pF = 0.4)

150 Vac

 

 

Motor, ac, 1/6 hp

250 Vac

Tungsten Lamp, 360 W

120 Vac

RS-232

Communications

Option -C2: RS-232 (one-to-one) Communications

 

RCV

XMT

SIG GND

 

RS

 

232

 

 

 

 

 

 

 

485

 

B(-)

A(+)

SIG GND

RS

 

 

RCV

XMT

SIG GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

1

 

1

 

 

2

23

24 12

3

 

13

Option Description: Provides a one-to-one connection between the controller and an RS-232 port. Computers, PLCs, or dumb terminals may be used to set and access controller data.

1

Image 4
Contents Series Omega.comTM Table of Contents Option -C2 RS-232 one-to-one Communications Option -AL1, -AL2 Relay, N.O. Alarm OutputLoad Type Voltage Limit Options -XP1, -XP2, -XP3, -XP4 Transducer Power Supply Option -C4 RS-485 one-to-many CommunicationsOptions -PVSV1, -PVSV2 Process Output Options -DIC, -RSP4, -RSP5, -RSP6, -RSP7 Remote SetpointOption -DIC Options -RSP4, -RSP5, -RSP6, -RSP7With Wiring diagram for digital communications Remote Communications OptionsOmega+ Protocol Message FormatsStart Char ZoneError TypeParam Type character Message TypeChksum END CharWrite Command to Controller Read Command to ControllerRead Response from Controller Write Response from Controller Auxiliary Command to ControllerAuxiliary Response from Controller Read Request Request Message DescriptionWrite Request Field Description TypeResponse Messages Auxiliary Command RequestField Description Read Response Write ResponseAuxiliary Command Response CN8240/CN8260 Parameter CodesNumber Name Read Write Data Field Value RAM, EepromDigital Communications Option PID Digital Communications Option Digital Communications Option Digital Communications Option Auxiliary Commands Or RTD w/ DecimalCommand Clear Latched Alarms Parameter # Description Command Retrieve Display Parameter # DescriptionRequest Data Fields CN8240 & CN8260 Series Communications & Options CN8240 & CN8260 Series Communications & Options CN8240 & CN8260 Series Communications & Options Warranty / Disclaimer Temperature