Bard 2100-404E Installation Instructions, Wall Mounting Information, Mounting the Unit

Page 8

INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1.Two holes, for the supply and return air openings, must be cut through the wall as shown in Figure 3.

2.On wood-frame walls, the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration.

WARNING

Fire hazard can result if 1/4 inch clearance to combustible materials for supply air duct is not maintained. See Figure 3.

3.Concrete block walls must be thoroughly inspected to insure that they are capable of carrying the weight of the installing unit.

MOUNTING THE UNIT

1.These units are secured by wall mounting brackets which secure the unit to the outside wall surface at both sides. A bottom mounting bracket is provided for ease of installation, but is not required.

2.The unit itself is suitable for “0” inch clearance, but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1/4 inch clearance to combustible material. If a combustible wall, use a minimum of 28½" x 8½" dimensions for sizing. However, it is generally recommended that a 1-inch clearance is used for ease of installation and maintaining the required clearance to combustible material.

WARNING

Failure to provide the 1/4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire.

3.Locate and mark lag bolt locations and bottom mounting bracket location. See Figure 3.

4.Mount bottom mounting bracket, if used The supply air opening would then be 30" x 10". See Figures 3 and 4 for details.

5.Hook top rain flashing under back bend of top. Top rain flashing is shipped secured to the right side of the back.

6.Position unit in opening and secure with 5/16 lag bolts; use 7/8 inch diameter flat washers on the lag bolts.

7.Secure rain flashing to wall and caulk across entire length of top. See Figure 3.

8.For additional mounting rigidity, the return air and supply air frames or collars can be drilled and screwed or welded to the structural wall itself (depending upon wall construction). Be sure to observe required clearance of combustible wall.

9.On side-by-side installations, maintain a minimum of 20 inches clearance on right side to allow access to heat strips and control panel and to allow proper airflow to the outdoor coil. Additional clearance may be required to meet local or national codes.

TOP OUTLET ONLY

1.Remove airframe angles from the back of the unit.

2.Coat angles with two 1/8" beads of silicone as shown. Silicone is shipped in the control panel. See Figure 5.

3.Secure angles to the top of the unit with 14 screws provided. Use of prepunched holes provided. Do not relocate. See Figure 5.

4.After installation duct work, seal around airframe and duct work to provide a rain tight seal.

5.It is strongly recommended, but not required, that this unit be installed under a soffit area large enough to shield the top of the unit. See Figure 6.

WIRING — MAIN POWER

Refer to the unit rating plate for wire sizing information and maximum fuse or “HACR Type” circuit breaker size. Each outdoor unit is marked with a “Minimum Circuit Ampacity”. This means that the field wiring used must be sized to carry that amount of current. Depending on the installed KW of electric heat, there may be two field power circuits required. If this is the case, the unit serial plate will so indicate. All models are suitable only for connection with copper wire. Each unit and/or wiring diagram will be marked “Use Copper Conductors Only”. These instructions must be adhered to. Refer to the National Electrical Code (NEC) for complete current carrying capacity data on the various insulation grades of wiring material. All wiring must conform to NEC and all local codes.

Manual 2100-404E Page 8 of 19

Image 8
Contents Wall Mounted Contents Getting Other Information and Publications For More INFORMATION, Contact These PublishersAIR Conditioner Wall Mount Model Nomenclature Electrical SpecificationsWall Mount General Information Dimensions of Basic Unit Nominal Electric Heat Table Shipping DamageGeneral Fresh AIR Damper Assembly Duct WorkFilters Fresh AIR IntakeInstallation Instructions Wiring Main PowerWall Mounting Information Mounting the UnitWiring LOW Voltage Wiring Wall Thermostat Thermostat Wire SizeLOW Voltage Connections Operating Voltage RangeMounting Instructions WALL-MOUNTING Instructions Common WALL-MOUNTING Installations Electric Heat Clearance LOW Voltage Wiring Start UP Pressure Service Ports Compressor Control ModuleTroubleshooting FAN Blade Setting DimensionsRemoval of FAN Shroud Refrigerant ChargeOutdoor Temperature F Cooling PressureOptional Accessories WA302-A WA372-A WA302-B WA372-B WA302-C WA372-C

2100-404E specifications

The Bard 2100-404E is an advanced heating and cooling unit designed to provide efficient climate control solutions for various applications. This innovative model is renowned for its compact design and high performance, making it suitable for both residential and commercial settings.

One of the standout features of the Bard 2100-404E is its energy efficiency. It comes equipped with a high-efficiency compressor that not only helps in reducing energy consumption but also lowers operational costs. This model adheres to the latest energy efficiency standards, ensuring that users benefit from significant savings on their utility bills.

The unit utilizes environmentally friendly refrigerants, which contribute to its eco-friendly profile. By minimizing its carbon footprint, the Bard 2100-404E aligns with contemporary environmental standards and regulations, making it a responsible choice for conscientious consumers.

Another notable characteristic of the Bard 2100-404E is its robust construction and durability. The unit is built with high-quality materials designed to withstand harsh weather conditions, ensuring longevity and reliable performance over time. This makes it ideal for installation in various environments, including those subjected to extreme temperatures.

The Bard 2100-404E features a user-friendly digital control panel that allows for easy adjustments and monitoring of settings. Users can effortlessly customize their heating and cooling preferences, optimizing comfort within their spaces. The system also includes programmable settings, enhancing convenience and energy savings.

In terms of technologies, the Bard 2100-404E incorporates modern HVAC advancements such as variable speed fans and multi-zone capabilities. These features result in enhanced temperature control and improved indoor air quality, ensuring that every corner of a space is evenly conditioned.

Other characteristics include relatively low noise levels, making the unit suitable for installation in noise-sensitive areas. Additionally, the Bard 2100-404E is designed for easy maintenance, with accessible components that simplify servicing and repairs.

In conclusion, the Bard 2100-404E represents a smart investment for those seeking an efficient, durable, and versatile heating and cooling solution. With its energy-saving features, environmental consciousness, and cutting-edge technologies, it stands out as a premier choice for modern climate control needs.