Friedrich R-410A service manual Explosion Hazard, Freeze Hazard

Page 21

3.After all refrigerant has been recovered, disconnect suction and discharge lines from the compressor and remove compressor. Be certain to have both suction and discharge process tubes open to atmosphere.

4.Carefully pour a small amount of oil from the suction

stub of the defective compressor into a clean container.

5.Using an acid test kit (one shot or conventional kit), test the oil for acid content according to the instructions with the kit.

6.If any evidence of a burnout is found, no matter how slight, the system will need to be cleaned up following proper procedures.

7.Install the replacement compressor.

WARNING

EXPLOSION HAZARD

The use of nitrogen requires a pressure regulator. Follow all safety procedures and wear protective safety clothing etc.

Failure to follow proper safety procedures result in serious injury or death.

8.Pressurize with a combination of R-410A and nitrogen and leak test all connections with an electronic or Halide leak detector. Recover refrigerant and repair any leaks found.

Repeat Step 8 to insure no more leaks are present.

9.Evacuate the system with a good vacuum pump capable of a fi nal vacuum of 200 microns or less. The system should be evacuated through both liquid line and suction line gauge ports. While the unit is being evacuated, seal all openings on the defective compressor. Compressor manufacturers will void warranties on units received not properly sealed. Do not distort the manufacturers tube connections.

CAUTION

FREEZE HAZARD

Proper safety procedures must be followed, and proper protective clothing must be worn when working with liquid refrigerant.

Failure to follow these procedures could result in minor to moderate injury.

10.Recharge the system with the correct amount of refrigerant. The proper refrigerant charge will be found on the unit rating plate. The use of an accurate measuring device, such as a charging cylinder, electronic scales or similar device is necessary.

SPECIAL PROCEDURE IN THE CASE OF MOTOR COMPRESSOR BURNOUT

WARNING

ELECTRIC SHOCK HAZARD

Turn off electric power before service or installation.

Failure to do so may result in personal injury, or death.

WARNING

HIGH PRESSURE HAZARD

Sealed Refrigeration System contains refrigerant and oil under high pressure.

Proper safety procedures must be followed, and proper protective clothing must be worn when working with refrigerants.

Failure to follow these procedures could result in serious injury or death.

WARNING

EXPLOSION HAZARD

The use of nitrogen requires a pressure regulator. Follow all safety procedures and wear protective safety clothing etc.

Failure to follow proper safety procedures result in serious injury or death.

1.Recover all refrigerant and oil from the system.

2.Remove compressor, capillary tube and fi lter drier from the system.

3.Flush evaporator condenser and all connecting tubing with dry nitrogen or equivalent. Use approved fl ushing agent to remove all contamination from system. Inspect suction and discharge line for carbon deposits. Remove and clean if necessary. Ensure all acid is neutralized.

4.Reassemble the system, including new drier strainer and capillary tube.

5.Proceed with step 8-10 on previous section.

20

Image 21
Contents Hazardous Duty Room Air Conditioner Table Of Contents Electrical Hazards Your safety and the safety of others are very importantMechanical Hazards Refrigeration System HazardsIntroduction Fire Damage HazardsWater Damage Hazards Unit Identification 15 M 3 0 a aIdeal applications Hazardgard ApplicationCooling Performance Data Specifications and Performance DataElectrical Data Electric Shock HazardFire Hazard Control Panel Hazardgard Special FeaturesMechanical components Component DefinitionsComponent Testing Capacitor Check with Capacitor AnalyzerCapacitor Connections High Pressure Hazard ThermostatRefrigeration system under high pressure 410A Sealed System Repair ConsiderationsEquipment Required 410A Sealed Refrigeration System RepairsEquipment Must be Capable Risk of Electric ShockMethod Of Charging / Repairs Burn HazardFreeze Hazard Overcharged Refrigerant Systems Undercharged Refrigerant SystemsRestricted Refrigerant System Compressor Checks Single Phase Resistance Test Compressor ReplacementRecommended procedure for compressor replacement High TemperaturesExplosion Hazard Routine Maintenance Sleeve / Drain Front CoverClearances Outdoor Temperature Indoor TemperaturesElectrical CompressorTroubleshooting Only. Cycles on Problem Possible Cause SH15M30 SH20M30 Electromechanical Control Cool only ModelsLimited ONE Year Parts Warranty Hazardgard Room AIR Conditioners Limited WarrantyTechnical Support Contact Information Page Friedrich AIR Conditioning CO
Related manuals
Manual 32 pages 34.87 Kb Manual 47 pages 33.75 Kb Manual 16 pages 9.01 Kb Manual 87 pages 18.35 Kb

R-410A specifications

Friedrich R-410A is an advanced refrigerant widely used in HVAC (Heating, Ventilation, and Air Conditioning) systems, known for its high efficiency and environmental friendliness. As a hydrofluorocarbon (HFC) blend, R-410A has become the preferred alternative to R-22, which is being phased out due to its ozone-depleting potential. One of the main features of R-410A is its high latent heat of vaporization, which allows for efficient heat transfer and improved cooling performance in air conditioning units.

Technologically, R-410A operates at higher pressures than older refrigerants, meaning systems designed for R-410A need to be built with more robust components to safely handle these pressures. This results in a more compact system design that offers enhanced performance and reliability. The dual-component nature of R-410A—composed of difluoromethane (R-32) and pentafluoroethane (R-125)—provides an optimal balance of thermodynamic properties, leading to superior energy efficiency, especially in variable speed applications.

In terms of characteristics, R-410A has a higher cooling capacity, which enables HVAC systems to effectively cool larger spaces or run more efficiently when cooling smaller areas. The refrigerant is non-toxic and non-flammable, which enhances safety during its use. In addition, R-410A has a lower global warming potential relative to other refrigerants, making it a more environmentally responsible choice for modern cooling systems.

Moreover, R-410A systems typically require less refrigerant charge due to their efficiency, contributing to reduced greenhouse gas emissions. The adoption of R-410A aligns with regulatory trends aimed at minimizing the environmental impact of refrigerants in cooling applications.

Overall, the Friedrich R-410A refrigerant embodies a combination of technology and environmental stewardship, making it a cornerstone of contemporary HVAC design. Its ability to provide effective and energy-efficient cooling solutions while being compliant with modern environmental regulations positions R-410A as the refrigerant of choice for engineers and installers focused on sustainability and performance in air conditioning systems.