Friedrich PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS PE Series Chassis Specifications

Page 2

PE Series Chassis Specifications

 

M O D E L S :

 

 

PE07K

PE07R

PE09K

PE09R

PE12K

PE12R

PE15K

PE15R

 

 

 

 

 

 

 

 

 

 

 

 

P E R F O R M A N C E

D A T A :

 

 

 

 

 

 

 

Cooling Btuh.

 

7500/7300

7500

9200/9000

9200

12000/11800

12000

15000/14800

15000

 

Cooling Power (W)

 

615/598

615

814/796

814

1091/1073

1091

1579/1578

1579

 

EER

 

 

12.2

12.2

11.3

11.3

11.0

11.0

9.5

9.5

 

Dehumidification (Pts/h)

 

 

2.1

2.1

2.7

2.7

3.8

3.8

5.5

5.5

 

Sensible Heat Ratio

 

 

0.76

0.76

0.75

0.75

0.72

0.72

0.72

0.72

 

E L E C T R I C A L D A T A :

 

 

 

 

 

 

 

 

Voltage (1 Ph, 60Hz)

 

 

230/208

265

230/208

265

230/208

265

230/208

265

 

Voltage Range

 

 

253-198

292-239

253-198

292-239

253-198

292-239

253-198

292-239

 

Current (Amps) (A)

 

 

3.0

3.0

3.9

3.9

5.1

5.1

6.6

6.6

 

Power Factor

 

 

0.9

0.9

0.9

0.9

0.9

0.9

0.9

0.9

 

Amps L.R

 

 

18

18

22.2

22.2

26.3

26.3

38

38

 

Amps F.L.

 

 

3

3

3.9

3.9

5.1

5.1

6.8

6.8

 

Horsepower

 

 

1/15

1/15

1/12

1/12

1/10

1/10

1/10

1/10

 

A I R F L O W

D A T A :

 

 

 

 

 

 

 

 

Indoor CFM

 

 

250

250

300

300

325

325

350

350

 

Vent CFM

 

 

60

60

60

60

70

70

70

70

 

P H Y S I C A L

D A T A :

 

 

 

 

 

 

 

 

Dimensions (HxWxD) (In.)

 

16x42x13.75

16x42x13.75

16x42x13.75

16x42x13.75

16x42x13.75

16x42x13.75

16x42x13.75

16x42x13.75

 

Net Weight

 

 

105

105

112

112

120

120

125

125

 

Shipping Weight

 

 

123

123

130

130

138

138

143

143

 

R-22 Charge

 

 

27

27

32

32

31

31

34

34

PH Series Chassis Specifications

 

M O D E L S :

 

 

PH07K

 

PH07R

PH09K

PH09R

PH12K

PH12R

PH15K

PH15R

 

 

 

 

 

 

 

 

 

 

 

 

 

P E R F O R M A N C E

D A T A :

 

 

 

 

 

 

 

Cooling Btuh.

 

7200/7000

 

7200

9100/8900

9100

12000/11800

12000

14700/14500

14700

 

Cooling Power (W)

 

595/579

 

595

805/788

805

1121/1103

1121

1581/1559

1581

 

EER

 

 

12.1

 

12.1

11.3

11.3

10.7

10.7

9.3

9.3

 

Heating Btuh

 

6400/6200

 

6400

8100/7900

8100

10800/10600

10800

13500/13300

13500

 

COP

 

 

3.3

 

3.3

3.2

3.2

3.1

3.1

2.8

2.8

 

Dehumidification (Pts/h)

 

 

2.1

 

2.1

2.7

2.7

3.8

3.8

5.5

5.5

 

Sensible Heat Ratio

 

 

0.76

 

0.76

0.75

0.75

0.72

0.72

0.72

0.72

 

E L E C T R I C A L D A T A :

 

 

 

 

 

 

 

 

 

Voltage (1 Ph, 60Hz)

 

230/208

 

265

230/208

265

230/208

265

230/208

265

 

Voltage Range

 

253-198

 

292-239

253-198

292-239

253-198

292-239

253-198

292-239

 

Current (Amps) (A)

 

 

3.0

 

3.0

3.9

3.9

5.1

5.1

6.6

6.6

 

Power Factor

 

 

0.9

 

0.9

0.9

0.9

0.9

0.9

0.9

0.9

 

Amps L.R

 

 

18

 

18

22.2

22.2

26.3

26.3

38

38

 

Amps F.L.

 

 

3

 

3

3.9

3.9

5.1

5.1

6.8

6.8

 

Horsepower

 

 

1/15

 

1/15

1/12

1/12

1/10

1/10

1/10

1/10

 

A I R F L O W

D A T A :

 

 

 

 

 

 

 

 

 

Indoor CFM

 

 

250

 

250

300

300

325

325

350

350

 

Vent CFM

 

 

60

 

60

60

60

70

70

70

70

 

P H Y S I C A L

D A T A :

 

 

 

 

 

 

 

 

 

Dimensions (HxWxD)(In.)

 

16x42x13.75

 

16x42x13.75

16x42x13.75

16x42x13.75

16x42x13.75

16x42x13.75

16x42x13.75

16x42x13.75

 

Net Weight

 

 

105

 

105

112

112

120

120

125

125

 

Shipping Weight

 

 

123

 

123

130

130

138

138

143

143

 

R-22 Charge

 

 

27

 

27

30

30

28

28

41

41

250 V Receptacles and Fuse Types

AMPS

15

20

30

HEATER SIZE

0, 2.5 kW

3.4 kW

5.0 kW

 

 

 

 

RECEPTACLE

 

 

 

 

 

 

 

2

Image 2
Contents Product Profile PE Series Chassis Specifications PH Series Chassis SpecificationsExtended Heating Performance Extended Cooling Performance, PE07/09/12/15Extended Cooling Performance, PH07/09/12/15 Electric Heat Data, PE/PH 12/15K/R Typical Unit Components and DimensionsElectric Heat Data, PE/PH 07/09K/R WallMaster PTAC/PTHP Model Identification GuideTypical Wall Sleeve Installation Pxws Extended Wall Sleeve Installation and Sealant Locations PxweExternal Drain Internal Drain Kit Location and Installation PXDR10Architectural Louver Installation Pxaa WallMaster PTAC/PTHP Engineering Specifications Friedrich Ptac Accessories New Construction AccessoriesAdditional Accessories Chassis OptionsRevised 8/01 Wallmaster P-SERIES Packaged Terminal AIR Conditioners Multiple solutions

PACKAGED TERMINAL AIR CONDITIONERS AND HEAT PUMPS specifications

Friedrich Packaged Terminal Air Conditioners (PTACs) and Heat Pumps represent a cutting-edge solution for climate control in a variety of settings, especially in hotels, apartments, and commercial spaces. These units are designed to provide individual room temperature management, offering both heating and cooling options to ensure comfort year-round.

One of the standout features of Friedrich PTACs is their energy efficiency. These units often meet or exceed ENERGY STAR certification, which signifies superior efficiency compared to traditional models. This efficiency translates to lower energy bills and a reduced environmental footprint, making them a sustainable choice for modern building owners.

Friedrich utilizes advanced technologies in their PTAC units to enhance performance and reliability. This includes features like variable-speed compressors that adjust cooling and heating output based on real-time room demands, leading to more consistent temperatures and improved energy savings. Additionally, some units come equipped with digital controls and remote management capabilities, allowing users to easily monitor and adjust settings from a distance.

Another key characteristic of Friedrich PTACs is their quiet operation. By incorporating sound-reducing technologies and design features, these units minimize operational noise, creating a more pleasant environment for occupants. This is particularly important in settings like hotels and hospitals, where peace and quiet are paramount.

Friedrich's commitment to durability is evident in their robust construction. The units are built with high-quality materials designed to withstand the rigors of constant use, ensuring longevity. The design also includes easily accessible components for convenient maintenance and servicing, which helps to further extend the life of the unit.

Moreover, Friedrich offers a variety of models tailored to diverse installation needs. With options for different capacities, styles, and aesthetic finishes, building owners can find the perfect match for their spaces without sacrificing performance.

In conclusion, Friedrich Packaged Terminal Air Conditioners and Heat Pumps are an excellent choice for anyone looking to enhance indoor climate control. With their energy efficiency, advanced technologies, quiet operation, and durable construction, they set a high standard in the HVAC industry, ensuring comfort for occupants while also addressing the growing demand for environmentally sustainable solutions.