INSTALLATION

 

 

 

 

 

 

 

 

 

 

 

A-1

 

 

 

 

Technical Specifications - Invertec V250-S - K1436-1, K1437-1 & K1437-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THREE PHASE

 

 

 

 

 

SINGLE PHASE

 

 

 

 

 

Standard

 

 

 

 

 

 

Input Current

 

 

 

Standard

 

 

 

Input Current

 

 

 

 

 

Voltage

 

 

 

 

 

 

 

at Rated Output

Model

 

 

Voltage

 

 

 

at Rated Output

Model

 

 

208/230/460

60Hz

 

 

 

 

 

34/32/16

 

60Hz

 

 

208/230/460 60Hz

 

 

 

59/57/29

 

60Hz

 

 

200/220/400/440 50/60Hz

 

35/33/18/17

 

50/60 Hz

 

 

200/220/400/440 50/60 Hz

 

58/58/30/30

 

50/60 Hz

 

 

 

380-415 50Hz

 

 

 

 

 

 

 

20/18

 

50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RATED

 

 

OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THREE PHASE

 

 

 

 

 

SINGLE PHASE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Volts at

 

 

 

 

 

 

 

 

 

 

 

Volts at

 

 

 

 

 

Duty Cycle(1)

 

 

Amps

 

 

Rated Amps

 

Model

 

 

Duty Cycle(1)

 

Amps

 

Rated Amps

 

Model

 

 

35% Duty Cycle

 

250

 

 

 

 

30

 

60Hz

 

 

35% Duty Cycle

 

250

 

 

27-30

 

60Hz

 

 

60% Duty Cycle

 

200

 

 

 

 

28-32

 

60Hz

 

 

60% Duty Cycle

 

200

 

 

28-32

 

60Hz

 

 

100% Duty Cycle

 

165

 

 

 

 

26.5

 

60Hz

 

 

100% Duty Cycle

 

165

 

 

26.5

 

60Hz

 

 

35% Duty Cycle

 

250

 

 

 

 

28-30

 

50/60Hz

 

 

35% Duty Cycle

 

250

 

 

26-30

 

50/60Hz

 

 

60% Duty Cycle

 

200

 

 

 

 

29-32

 

50/60Hz

 

 

60% Duty Cycle

 

200

 

 

28-32

 

50/60Hz

 

 

100% Duty Cycle

 

165

 

 

 

 

26.5

 

50/60Hz

 

 

100% Duty Cycle

 

165

 

 

26.5

 

50/60Hz

 

 

35% Duty Cycle

 

250

 

 

 

 

30

 

50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60% Duty Cycle

 

200

 

 

 

 

28

 

50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100% Duty Cycle

 

165

 

 

 

 

26

 

50Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THREE PHASE

 

 

 

 

 

SINGLE PHASE

 

 

 

 

 

Welding

 

 

 

 

 

 

 

 

 

 

 

Constant Open

 

Welding

 

 

 

 

 

Constant Open

 

 

Current Range

 

 

 

 

 

 

 

 

Circuit Voltage

 

Current Range

 

 

 

 

 

Circuit Voltage

 

 

 

1-250 Amps

 

 

 

 

 

 

 

 

 

 

65-80 VDC

 

1-250 Amps

 

 

 

 

 

65-80 VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RECOMMENDED INPUT WIRE AND FUSE SIZES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

THREE PHASE

 

 

 

 

 

SINGLE PHASE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type 75°C

 

 

 

 

 

 

 

 

 

 

 

 

 

Type 75°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type 75°C

Copper

 

 

 

 

 

 

 

 

 

 

 

Type 75°C

Copper

 

 

 

 

 

 

 

Fuse

 

 

Input

 

Copper

Ground

 

 

 

 

Fuse

 

Input

 

Copper

Ground

 

 

 

 

 

(Superlag)

Ampere

 

Wire in

Wire in

 

 

 

(Superlag)

Ampere

 

Wire in

Wire in

 

 

 

Input

 

 

or

 

 

Rating

 

Conduit

Conduit

 

 

Input

 

or

 

Rating

 

Conduit

Conduit

 

 

 

Voltage

 

Breaker

 

 

 

 

on

 

AWG (IEC)

AWG (IEC)

 

 

Voltage

 

Breaker

 

 

on

 

AWG (IEC)

AWG (IEC)

 

 

Frequency(2)

 

 

Size

 

Nameplate

 

Sizes

Sizes

 

 

Frequency(2)

 

Size

 

Nameplate

 

 

Sizes

Sizes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/60

 

 

 

50

 

 

 

 

34

 

 

10 (6mm2)

10 (6mm2)

 

 

208/60(3)

 

80

 

 

 

59

 

8 (8.4mm2)

10 (6mm2)

 

 

230/60

 

 

 

50

 

 

 

 

32

 

 

10(6mm2)

10 (6mm2)

 

 

230/60(3)

 

80

 

 

 

57

 

8 (8.4mm2)

10 (6mm2)

 

 

460/60

 

 

 

30

 

 

 

 

16

 

 

10 (6mm2)

10 (6mm2)

 

 

460/60

 

40

 

 

 

29

 

10 (6mm2)

10 (6mm2)

 

 

200/50/60

 

 

50

 

 

 

 

35

 

 

10 (6mm2)

10 (6mm2)

 

 

200/50/60

 

80

 

 

 

58

 

8 (8.4mm2)

10 (6mm2)

 

 

220/50/60

 

 

50

 

 

 

 

33

 

 

10 (6mm2)

10 (6mm2)

 

 

220/50/60

 

80

 

 

 

58

 

8 (8.4mm2)

10 (6mm2)

 

 

400/50/60

 

 

30

 

 

 

 

18

 

 

12 (4mm2)

12 (4mm2)

 

 

400/50/60

 

40

 

 

 

30

 

10 (6mm2)

10 (6mm2)

 

 

440/50/60

 

 

30

 

 

 

 

17

 

 

12 (4mm2)

12 (4mm2)

 

 

440/50/60

 

40

 

 

 

30

 

10 (6mm2)

10 (6mm2)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PHYSICAL DIMENSIONS

Height

Width

Depth

Weight

15.0 in.

9.1 in.

19.7 in.

36 lbs.

381 mm

231 mm

500 mm

17 Kg

 

 

 

(1) Based on a 10 min. period.

(2) Input voltage must be within ±10% of rated value.

 

(†) 200 & 208VAC input may not meet NEMA/IEC specifications at 250 Amps.

INVERTEC V250-S

Image 8
Contents INVERTECV250-SFebruary Safety California Proposition 65 WarningsElectric Shock can kill Cylinder may explode if damaged Précautions DE Sûreté Sûreté Pour Soudage a L’ArcThank You Invertec V250-STable of Contents Three Phase InstallationThree Phase Single Phase Technical Specifications Invertec V250-S K1437-2 Input Connections Safety PrecautionsSelect Suitable Location Power Input Connection for 50/60 HZ Machines Input Voltage Reconnect ProcedureInput Fuse and Supply Wire Remote Control Receptacle Output ConnectionsQuick Disconnect Plugs Output CablesGeneral Description Safety InstructionsOperation Controls and Settings Figure B.1 Case Front ControlsConstant Current Processes Manual ARC Welding StickAIR Carbon ARC Cutting TIG WeldingThermal Protection Parallel OperationOverload Protection Accessories Options / AccessoriesRemote Controls Cable PlugsMaintenance Input Filter Capacitor Discharge ProcedureRoutine Maintenance Filter Capacitor ConditioningFigure D.2 Location of Maintenance Components Troubleshooting & Repair PC Board Troubleshooting ProceduresSymptoms Possible AreasTroubleshooting & Repair Troubleshooting & Repair See Installation Section of this Troubleshooting & Repair Welding Problems Diagrams Wiring DIAGRAM- Codes 10102Wiring Diagram Invertec V250-S Electrical Diagrams Electrical Diagrams Wiring DIAGRAM- CodeDimension Print Invertec V250-S How To Read Shop Drawings Basic CoursePrecaucion Warnung