Friedrich SH15L30-A manual Troubleshooting Problem Possible Cause To Correct, Unit does not RUN

Page 11

TROUBLESHOOTING

PROBLEM

POSSIBLE CAUSE

TO CORRECT

 

Power disconnected.

Check power source.

 

System switch in “Off”

Set switch correctly.

 

position.

 

 

 

Branch circuit fuse blown or

Replace fuse, reset breaker. If repeats, check fuse

 

or breaker size. Check for shorts in unit wiring and

UNIT DOES NOT RUN.

circuit breaker tripped.

components.

 

 

 

Inoperative system switch.

Test for continuity.

 

Loose or disconnected wiring

Check wiring and connections.

 

at switch.

Connect per wiring diagram.

 

Inoperative switch (On-Off).

Test for continuity, 3 and 2, 5 and 6.

 

 

 

 

Dirty Filter.

Clean as recommended in Owner’s Manual.

 

Restricted air flow.

Check for dirty or obstructed coil - clean as required.

 

Inoperative thermostat.

Test for shorted thermostat or stuck contacts.

EVAPORATOR COIL

Short of refrigerant.

De-ice coil and check for leak.

FREEZES UP.

 

 

 

De-ice coil. Check temperature differential across coil.

 

 

 

Partially restricted capillary.

Touch test coil return bends for same temperature. Test for

 

 

low running current.

 

Inoperative fan motor.

Test and replace if inoperative.

 

 

 

 

Excessive heat load.

Test cooling performance of unit. Unit undersized.

COMPRESSOR RUNS

Restriction in line.

Check for partially iced coil. Check temperature split

across coil.

 

CONTINUALLY.

 

Check for presence of oil on silver soldered connections.

DOES NOT CYCLE

Refrigerant leak.

Check for partially iced coil. Check split across coil.

OFF.

 

Check for low running amperage.

 

Thermostat contacts stuck.

Check operation of thermostat. Replace if contacts

 

remain closed.

 

 

 

 

 

 

Loss of charge in thermostat

Place jumper across thermostat terminals. If unit

 

bulb.

operates, replace thermostat.

THERMOSTAT DOES

Loose or broken parts in

Check as above.

NOT TURN UNIT ON.

thermostat.

 

 

Incorrect wiring.

Connect per wiring diagram.

 

System switch open.

Test for continuity at switch terminals 2 and 3.

 

 

 

 

Thermostat set at coldest

Turn to highest temperature setting to see of unit will cycle

 

point

off.

THERMOSTAT DOES

Thermostat contacts stuck.

Disconnect power to the unit. Remove cover of thermostat

NOT TURN UNIT OFF.

and check if contact is stuck, if so replace thermostat.

 

 

Switch (On - Off) shorted.

Test switch for open contacts at terminals 2 and 3 with

 

switch in “Off” position.

 

 

11

Image 11
Contents Service & Parts Manual Table of Contents Performance Data Cooling Line Voltage Overload Component Operation and TestingTesting Procedures CompressorsFAN Motor Test Ground TestChecking Compressor Efficiency Range CAPACITOR, RUNCapacitor Test ThermostatTest Equipment Must be Capable LOW Ambient Bypass Valve FigureSealed Refrigeration System Repairs Equipment Required Special Procedures in the Case of Compressor Motor Burnout Hermetic Component ReplacementRefrigerant Charge Rotary Compressor Special Troubleshooting and ServiceUnit does not RUN Troubleshooting Problem Possible Cause To CorrectProblem Possible Cause To Correct TroubleshootingFAN Motor does Models SH15L30-A, SH20L30-A, SH20L50-A Wiring DiagramHazardgard Cabinet Parts Hazardgard Chassis Parts Description Part NO# Models Code Electrical Parts Hazardgard Parts ListOptional Accessory Items Page Use Factory Certified Parts