Friedrich SH20L30-A, SH20L50-A, SH15L30-A manual Test

Page 7

TEST

Remove the wires from the thermostat. Turn the thermostat to its coldest position. Check to see if there is continuity between the two terminals. Turn the thermostat to its warmest position. Check continuity to see if the thermostat contacts open.

Note: The temperature must be within the range listed to check the thermostat. Refer to the troubleshooting section in this manual for additional information on thermostat testing.

7

Image 7
Contents Service & Parts Manual Table of Contents Performance Data Cooling Line Voltage Overload Component Operation and TestingTesting Procedures CompressorsChecking Compressor Efficiency Ground TestFAN Motor Test Range CAPACITOR, RUNCapacitor Test ThermostatTest Sealed Refrigeration System Repairs Equipment Required LOW Ambient Bypass Valve FigureEquipment Must be Capable Special Procedures in the Case of Compressor Motor Burnout Hermetic Component ReplacementRefrigerant Charge Rotary Compressor Special Troubleshooting and ServiceUnit does not RUN Troubleshooting Problem Possible Cause To CorrectProblem Possible Cause To Correct TroubleshootingFAN Motor does Models SH15L30-A, SH20L30-A, SH20L50-A Wiring DiagramHazardgard Cabinet Parts Hazardgard Chassis Parts Description Part NO# Models Code Electrical Parts Hazardgard Parts ListOptional Accessory Items Page Use Factory Certified Parts