COMPLAINT | CAUSE |
|
|
| REMEDY | |
|
|
|
|
|
| |
Compressor will not run, | Voltage |
| Check voltage. See the limits on the preceding. | |||
but fan motor runs. |
|
|
| page. If not within limits, call an electrician. | ||
|
|
|
|
|
| |
| Wiring |
| Check the wire connections, if loose, repair or | |||
|
|
|
| replace the terminal. If wires are off, refer to wiring | ||
|
|
|
| diagram for identification, and replace. Check wire | ||
|
|
|
| locations. If not per wiring diagram, correct. | ||
|
|
|
|
|
|
|
| Capacitor (Discharge |
| Check the capacitor. |
| ||
| capacitor before |
|
| |||
|
| Replace if not within ±10% of manufacturers | ||||
| servicing.) |
| ||||
|
| rating. Replace if shorted, open, or damaged. | ||||
|
|
|
| |||
|
|
|
|
|
| |
| Compressor |
| Check the compressor for open circuit or | |||
|
| ground. If open or grounded, replace the | ||||
|
|
|
| |||
|
|
|
| compressor. |
| |
|
|
|
|
|
| |
| Overload |
| Check the compressor overload, if externally | |||
|
| mounted. Replace if open. (If the compressor | ||||
|
|
|
| |||
|
|
|
| temperature is high, remove the overload, cool it, | ||
|
|
|
| and retest.) |
| |
|
|
|
|
|
| |
ROOM AIR CONDITIONER VOLTAGE LIMITS |
| |||||
|
|
|
|
|
|
|
NAME PLATE RATING |
| MINIMUM |
| MAXIMUM | ||
|
|
|
|
|
| |
115V |
|
| 103.5V |
| 126.5V | |
|
|
|
|
|
|
|
208/230V |
|
|
| 187V |
| 253V |
|
|
|
|
|
|
|