2.4.2 EVAPORATOR/CONDENSER

1.Remove the cabinet.

2.Discharge the refrigerant by using a refrigerant recovery system.

3.Remove the air guide upper. (Refer to Section 2.2.1)

4.After discharging the refrigerant completely, unbraze the interconnecting tube at the proper coil connections.

5.Remove the evaporator.

6.Re-install by referring to the procedures above.

2.4.3 CAPILLARY TUBE

1.Remove the cabinet.

2.Discharge the refrigerant by using a refrigerant recovery system.

3.Remove the air guide upper. (Refer to Section 2.2.1)

4.After discharging the refrigerant completely, unbraze the interconnecting tube of the capillary tube.

5.Remove the capillary tube.

6.Re-install by referring to the procedures above.

NOTES

Replacement of the refrigeration cycle.

1.When replacing the refrigeration cycle, be sure to discharge the refrigerant by using a refrigerant recovery system.

2.After discharging the unit completely, remove the desired components, and unbraze the pinch-off tubes.

3.Solder service valves into the pinch-off tube ports, leaving the valves open.

4.Solder the pinch-off tubes with service valves.

5.After completing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures.

6.Evacuate as follows:

6-1. Connect the vacuum pump, as illustrated in figure 21A.

6-2. Start the vacuum pump. Slowly open manifold valves A and B with two full turns counter- clockwise and leave the valves closed.

The vacuum pump is now pulling through valves A and B up to valve C by means of manifold and the entire system.

CAUTION : If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counter-clock-

wise. This will keep oil from foaming and being drawn into the vacuum pump.

6-3. Operate the vacuum pump for 20 to 30 min- utes, until 600 micron vacuum is obtained. Close valves A and B and observe vacuum gauge for a few minutes.

A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

6-4. Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 21B. Open valve C.

Discharge the line at the manifold connection. 6-5. The system is now ready for final charging.

7.Recharge as follows:

7-1. Rotary compressor systems are charged from the high-side. If the total charge cannot be put in the high-side, the balance will be put in the suction line through the access valve which is installed as the system is opened.

7-2. Connect the charging cylinder as shown in fig- ure 21B. With valve C open, discharge the hose at the manifold connection.

7-3. Open valve A and allow the proper charge to enter the system. Valve B is still closed.

7-4. If more charge is required, the high-side will not take it. Close valve A.

7-5. With the unit running, open valve B and add the balance of the charge.

a.Do not add the liquid refrigerant to the low- side.

b.Watch the low-side gauge, allow pressure to rise to 30 lbs.

c.Turn off valve B and allow the pressure to drop.

d.Repeat steps B and C until the balance of the charge is in the system.

7-6. When the unit is operating correctly, use the pinch-off tool with the unit still running and the clamp on the pinch-off tube. Using a tube cut- ter, cut the pinch-off tube about 2 inches from the pinch-off. Use sil-fos solder and solder the pinch-off tube closed. Turn off the unit,

allow unit to sit for a while and then test the leak- age of the pinch-off connection.

— 10—

Image 10
Contents Room Air Conditioner Service and Parts Manual Contents Specifications FeaturesPreface Locations of Controls Safety PrecautionsInsulation Resistance Test Front Grille Disassembly InstructionsMechanical Parts CabinetAIR Guide Upper AIR Handling PartsORIFICE, Turbo FAN and FAN AIR Guide Electrical PartsOverload Protector Thermistor CompressorCapacitor Control PanelRefrigerant Cycle Power CordCondenser EVAPORATOR/CONDENSER Capillary TubePulling Vacuum Troubleshooting Guide Outside Dimensions unit mmPiping System Condenser CoilsTroubleshooting Guide Unit is running but cooling is ineffectiveFails to Start Room AIR Conditioner Voltage Limits Replace if open. If the compressor temperature is Complaint Cause Remedy Circuit Diagram Model CP05A10, CP06A10Exploded View W0CZZService Parts List CP05A10CP06A10 Memo Use Factory Certified Parts

CP06A10, CP05A10 specifications

The Friedrich CP05A10 and CP06A10 are advanced air purifier models designed to enhance indoor air quality in both residential and commercial environments. These units utilize cutting-edge technologies and features that cater to the diverse needs of users looking to improve their indoor atmosphere.

One of the standout features of both models is the advanced HEPA filtration system. The High-Efficiency Particulate Air (HEPA) filter captures up to 99.97% of airborne particles as small as 0.3 microns. This includes allergens such as pollen, dust mites, pet dander, and mold spores, making it an ideal choice for allergy sufferers. Additionally, the CP05A10 and CP06A10 are equipped with a pre-filter that traps larger particles, extending the life of the HEPA filter and ensuring consistent performance.

Another key technology integrated into these purifiers is the activated carbon filter. This component effectively reduces odors from pets, cooking, and smoke, ensuring a fresher indoor environment. The combination of HEPA and activated carbon filtration technology allows these models to tackle both particulate matter and harmful gaseous pollutants.

The CP05A10 and CP06A10 also feature smart air quality sensors that continuously monitor the indoor air quality and automatically adjust the purification setting based on real-time measurements. This ensures that the air in the room remains clean without requiring constant manual adjustments. In terms of user-friendliness, both models come with a simple control panel and an intuitive design that allows for easy navigation through various settings.

In terms of design, Friedrich has crafted these models to be compact and aesthetically pleasing, making them suitable for various room sizes without compromising on performance. The CP05A10 is recommended for smaller rooms, while the CP06A10 is designed for larger areas, ensuring versatility in deployment.

Energy efficiency is another hallmark of the Friedrich CP05A10 and CP06A10. Both models are designed to operate quietly, making them perfect for nighttime use in bedrooms or other quiet spaces. With a low energy consumption rating, these purifiers provide users with a cost-effective solution to improving indoor air quality without significantly increasing energy bills.

In summary, the Friedrich CP05A10 and CP06A10 air purifiers embody a combination of advanced filtration technologies, user-friendly features, and stylish design, making them excellent choices for anyone looking to enhance their indoor air quality effectively and efficiently.