Timing Chart

Operation Timing after Power-ON

<Notes>
The above chart shows the timing from AC power-ON to command input.
Activate the external command input according to the above timing chart.
Caution
*1. In this term Servo-ON input (CN X5 SRV-ON:pin23) turns ON as a hard ware, but operation command
can not be received.
*2. Servo alarm output (CN X5 ALM:pin15) turns ON when the microcomputer's initialization is completed,
and the condition of no error is occurring. Servo-ON input turns ON after Servo alarm turns ON and the
main power supply is activated sufficiently.
*3. After Internal control power supply , protective functions are active from approx. 1.5 sec after the
start of initializing microcomputer. Please set the signals, especially for protective function, for
example over-travel inhibit input (CWL,CCWL) or emergency stop input (EMG-STP), so as to de-
cide their logic until this term.
ONOFF
Point setting
Approx. 100ms or more *1
MIN 10ms
Control 
power supply
(L1C,L2C)
Internal control 
power supply
Microcomputer
Main power supply
(L1, L2, L3)
Servo alarm output
(X5 Pin 15)
Servo-ON input
(X5 Pin 23)
Dynamic brake
Motor energized
BRK-OFF output 
(X5 Pin 36)
Point specifying input
(P1IN - P32IN)
Strobe signal
(STB)
OFF
OFF
ON
Reset ON
OFF ON
OFF ON
ONOFF
OFF (Brake engaged) ON
(Brake released)
OFFON
Not energized Energized
Approx. 10ms
or more
Approx. 10ms 
or more
Approx. 2s
Approx. 1.5s
Approx. 100 to 300ms
Activated
Initialize
Approx.
40ms
Approx. 2ms
Approx. 2ms
0ms or more
0s or more
*2
*3
*2