Parameter Setup

Standard default : < >

Servo￿

Title

Setup￿

 

Unit

 

 

 

 

Function/Content

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PrNo.

 

range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34

1st control

0 to 20000

￿

–￿

You can set up hysteresis width to be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

switching

<33>*

 

 

implemented above/below the judging

 

 

SV.Pr33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

hysteresis

 

 

 

level which is set up with SV.Pr33. Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

varies depending on the setup of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV.Pr34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV.Pr31 (1st control switching mode).

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1st gain

2nd gain

 

 

 

 

1st gain

 

 

 

 

 

Definitions of SV.Pr32 (Delay), SV.Pr33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Level) and SV.Pr34 (Hysteresis) are

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV.Pr32

 

 

 

 

 

explained in the fig. below.￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<Caution>￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The setup of SV.Pr33 (Level) and SV.Pr34 (Hysteresis) are valid as

 

 

 

 

 

absolute values (positive/negative).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

Position loop gain

0 – 10000￿ (setup

You

can

setup

the

e.g.)

 

 

 

 

 

 

 

 

 

 

166s Kp1(SV.Pr10)>Kp2(SV.Pr18)

 

switching time

<20>* value +1)￿ step-by-step switching

166

 

 

 

 

 

 

 

 

 

 

 

 

 

Kp1￿

 

 

 

 

 

 

166

 

 

166

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

x 166s

time

to the position

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

bold line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(SV.Pr10)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

loop gain only at gain

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SV.Pr35= 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

switching while the 1st

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

thin line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

and

the

2nd

gain

Kp2￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

switching is valid.￿

(SV.Pr18)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1st gain

 

 

 

 

 

 

 

 

 

 

2nd gain

 

 

 

 

1st gain

 

 

 

 

 

<Caution>￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The

switching time is

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

only valid when switching from small position gain to large position gain.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameters for Position Control

 

 

 

 

 

 

 

 

 

Standard default : < >

Servo￿

Title

Setup￿

 

 

 

Function/Content

 

 

 

 

PrNo.

range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

44￿

Numerator of

1 to 32767

￿You can set up the pulse counts to be fed out from the pulse output (X5 0A+ : Pin-

 

*￿

output pulse ratio￿

<10000>

￿21, 0A- : Pin-22, 0B+ : Pin-48, 0B- : Pin-49).￿

 

 

 

 

 

￿

￿

￿

 

• In the case that the encoder pulse is output (When the control mode is

 

 

 

 

the position control mode and SV.Pr46 = 0, 1).￿

 

 

 

 

45￿

Denominator of

0 to 32767

￿

 

 

 

 

 

• SV.Pr45=0 : ￿

 

 

 

 

 

 

 

*

output pulse ratio

<10000>

 

 

 

 

 

 

 

 

 

￿￿￿You can set up the output pulse counts per one motor revolution for each OA

 

 

 

 

 

 

 

 

 

 

 

 

 

and OB with the SV.Pr44 setup. Therefore the pulse output resolution after

 

 

 

 

 

 

 

quadruple can be obtained from the formula below.￿

 

 

 

 

 

 

 

 

￿ The pulse output resolution per one revolution = ￿

 

 

 

 

 

 

 

 

￿

SV.Pr44 (Numerator of output pulse ratio) X 4

 

 

 

 

 

 

 

 

• SV.Pr450 :￿

 

 

 

 

 

 

 

 

 

 

 

 

The pulse output resolution per one revolution can be divided by any ration

 

 

 

 

 

 

 

according to the formula below.￿

SV.Pr44 ￿

 

 

 

 

 

 

 

 

 

￿

 

 

 

 

 

 

 

 

 

 

 

(Numerator of output pulse ratio)￿

 

 

 

 

 

 

￿Pulse output resolution per one revolution

 

 

 

x Encoder resolution

 

 

 

 

 

 

 

SV.Pr45￿

 

 

 

 

 

 

￿

 

 

 

 

 

 

 

 

 

 

 

￿

 

(Denominator of output pulse ratio)

 

 

 

 

 

 

<Cautions>

￿

 

 

 

 

 

 

 

 

 

• The encoder resolution is 131072 [P/r] for the 17-bit absolute encoder, and

 

 

 

 

 

 

10000 [P/r] for the 5-wire 2500P/r incremental encoder.￿

 

 

 

 

 

 

 

 

• The pulse output resolution per one revolution cannot be greater than the

 

 

 

 

 

 

encoder resolution.￿

 

 

 

 

 

 

 

 

 

 

 

 

(In the above setup, the pulse output resolution equals to the encoder resolution.)￿

 

 

 

 

 

Z-phase is fed out once per one revolution of the motor.￿

 

 

 

 

 

 

 

 

When the pulse output resolution obtained from the above formula is multiple of 4,

 

 

 

 

 

Z-phase synchronizes with A-phase. In other case, the Z-phase width equals to

 

 

 

 

 

output with the encoder resolution, and becomes narrower than A-phase, hence

 

 

 

 

 

does not synchronize with A-phase.￿

 

 

 

 

 

 

 

 

 

￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Continue to the next page.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 