[Setting]

 

 

 

 

 

 

 

 

 

 

 

Standard default : < >

Servo￿

Title

Setup￿

Unit

 

 

 

 

Function/Content

 

 

 

PrNo.

 

range

 

 

 

 

 

 

 

 

 

 

 

64

Output signal

0 to 1￿

–￿

Set the function of the

positioning completion output/in-deceleration

 

 

selection

<0>

 

output pin (COIN/DCLON: CN X5 Pin 27).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup value￿

 

 

 

Description￿

 

 

 

 

 

 

 

 

<0>￿

 

COIN (Positioning completion output)￿

 

 

 

 

 

 

 

1

 

 

DCLON (In-deceleration output)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

65

Undervoltage error

0 to 1￿

–￿

You can select whether

or not

to

activate Err13

(Main power supply

 

 

response at main

<1>

 

under-voltage protection) function while the main power shutoff continues

 

 

power-off

 

 

for the setup of Pr6D (Main power-off detection time).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup value￿

Action of main power low voltage protection￿

 

 

 

 

 

 

 

￿

 

Turns the servo off according to SV.Pr67 (Error response

 

 

 

 

 

 

 

0￿

 

at main power-off).￿

 

 

 

 

 

 

 

 

 

￿

 

 

 

 

 

 

 

 

 

 

 

When the main power is shut off during Servo-ON, the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<1>

 

driver will trip due to Err13 (Main power supply under-

 

 

 

 

 

 

 

 

 

voltage protection).

 

 

 

 

 

 

 

 

 

<Caution>￿

 

 

 

 

 

 

 

 

 

 

 

 

This parameter is invalid when SV.Pr6D (Main power-off detection

 

 

 

 

 

time)=1000. Err13 (Main power supply under-voltage protection) is

 

 

 

 

 

triggered when setup of SV.Pr6D is long and P-N voltage of the main

 

 

 

 

 

converter falls below the specified value before detecting the main power

 

 

 

 

 

shutoff, regardless of the SV.Pr65 setup.

 

 

 

 

 

 

 

 

 

 

 

67

Error response at

0 to 9￿

–￿

When SV.Pr65 (Undervoltage error response at main power-off) is 0, you

 

 

main power-off

<0>

 

can set up,￿

 

 

 

 

 

 

 

 

 

 

 

 

 

1) the action during deceleration and after stalling￿

 

 

 

 

 

 

 

 

2) the clearing of deviation counter content￿

 

 

 

 

 

 

 

after the main power is shut off.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup￿

 

￿

Action

￿

Deviation counter￿

 

 

 

 

 

 

value￿

During deceleration￿

After stalling￿

content￿

 

 

 

 

 

 

 

<0>￿

 

DB￿

 

 

DB￿

Clear￿

 

 

 

 

 

 

 

1￿

 

Free-run￿

 

DB￿

Clear￿

 

 

 

 

 

 

 

2￿

 

DB￿

 

 

Free-run￿

Clear￿

 

 

 

 

 

 

 

3￿

 

Free-run￿

 

Free-run￿

Clear￿

 

 

 

 

 

 

 

4￿

 

DB￿

 

 

DB￿

Hold￿

 

 

 

 

 

 

 

5￿

 

Free-run￿

 

DB￿

Hold￿

 

 

 

 

 

 

 

6￿

 

DB￿

 

 

Free-run￿

Hold￿

 

 

 

 

 

 

 

7￿

 

Free-run￿

 

Free-run￿

Hold￿

 

 

 

 

 

 

 

8￿

 

Emergency stop￿

 

DB￿

Clear￿

 

 

 

 

 

 

 

9

 

Emergency stop

 

Free-run

Clear

 

 

 

 

 

 

(DB: Dynamic Brake action)￿

 

 

 

 

 

 

 

 

 

 

<Caution>￿

 

 

 

 

 

 

 

 

 

 

 

 

 

In case of the setup value of 8 or 9, torque limit during deceleration will be

 

 

 

 

 

 

limited by the setup value of SV.Pr6E (Emergency stop torque set up).

 

 

 

 

 

 

 

68

Error response

0 to 3￿

–￿

You can set up the action during deceleration or after stalling when some

 

 

action

<0>

 

error occurs while either one of the protective functions of the driver is

 

 

 

triggered.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setup￿

 

￿

Action

￿

Deviation counter￿

 

 

 

 

 

 

value￿

During deceleration￿

After stalling￿

content￿

 

 

 

 

 

 

 

<0>￿

 

DB￿

 

 

DB￿

Hold￿

 

 

 

 

 

 

 

1￿

 

Free-run￿

 

DB￿

Hold￿

 

 

 

 

 

 

 

2￿

 

DB￿

 

 

Free-run￿

Hold￿

 

 

 

 

 

 

 

3

 

Free-run

 

Free-run

Hold

 

 

 

 

 

 

(DB: Dynamic Brake action)￿

 

 

 

 

 

 

 

 

 

<Caution>￿

 

 

 

 

 

 

 

 

 

 

 

 

The content of the deviation counter will be cleared when clearing the

 

 

 

 

 

alarm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Setting

69

Page 69
Image 69
Panasonic A4P Series instruction manual Action of main power low voltage protection, Setup Action Deviation counter Value