[Setting]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard default : < >

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Servo￿

Title

Setup￿

 

Unit

 

 

 

 

Function/Content

 

 

 

 

 

PrNo.

 

range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6C￿

External

0 to 3￿

 

–￿

 

With this parameter, you can select either to use the built-in regenerative

 

 

*

regenerative

for￿

 

 

 

resistor of the driver, or to separate this built-in regenerative resistor and

 

 

 

 

 

externally install the regenerative resistor (between RB1 and RB2 of

 

 

 

resistor set up

A, B-frame￿

 

 

 

 

 

 

 

Connector CN X2 in case of A to D-frame, between P and B2 of terminal

 

 

 

 

<3>￿

 

 

 

 

 

 

 

 

block in case of E, F-frame).

 

 

 

 

 

 

 

 

 

 

for￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Regenerative resistor

￿

Regenerative processing and￿

 

 

 

 

 

 

 

 

 

Setup value￿

￿

 

 

regenerative resistor overload￿

 

 

 

 

 

C to F-frame￿

 

 

 

 

to be used

 

 

 

 

 

 

 

 

 

<0>￿

 

￿

 

 

 

 

￿

 

 

 

 

 

 

<0>

 

 

 

 

 

Regenerative processing circuit will be

 

 

 

 

 

 

 

 

(C, D, E and

￿Built-in resistor￿

activated and regenerative resistor overload

 

 

 

 

 

 

 

 

 

protection

will be triggered according to the

 

 

 

 

 

 

 

 

 

F-frame)￿

 

￿

 

built-in resistor (approx. 1% duty).￿

 

 

 

 

 

 

 

 

 

￿

 

￿

 

The driver trips due to regenerative overload

 

 

 

 

 

 

 

 

 

1￿

 

 

 

protection

(Err18),

when

regenerative

 

 

 

 

 

 

 

 

 

External resistor ￿processing

circuit is

activated

and its active

 

 

Setting

 

 

 

 

 

 

￿

 

￿

 

triggered.￿

 

 

 

 

 

 

 

 

 

 

 

￿

 

￿

 

ratio exceeds 10%, ￿

 

 

 

 

 

 

 

 

 

 

 

2￿

 

 

 

Regenerative processing circuit is activated,

 

 

 

 

 

 

 

 

 

External resistor ￿but no

regenerative

over-load

protection is

 

 

 

 

 

 

 

 

 

<3>￿

 

￿

 

Both regenerative processing circuit and

 

 

 

 

 

 

 

 

 

 

No resistor

regenerative protection are not activated, and

 

 

 

 

 

 

 

 

 

(A, B-frame)

 

built-in capacitor handles all regenerative

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

power.

 

 

 

 

 

 

 

 

 

 

 

 

 

<Remarks>￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Install an external protection such as thermal fuse when you use the

 

 

 

 

 

 

 

 

external regenerative resistor. ￿

 

 

 

 

 

 

 

 

 

 

 

 

 

Otherwise, the regenerative resistor might be heated up abnormally and

 

 

 

 

 

 

 

 

result in burnout, regardless of validation or invalidation of regenerative

 

 

 

 

 

 

 

 

over-road protection.￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<Caution>

 

 

￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When you use the built-in regenerative resistor, never to set up other

 

 

 

 

 

 

 

 

value than 0. Don't touch the external regenerative resistor.￿

 

 

 

 

 

 

 

 

External regenerative resistor gets very hot, and might cause burning.

 

 

 

 

 

 

 

 

 

 

 

6D￿

Main power-off

35 to 1000￿

2ms

 

You can set up the time to detect the shutoff while the main power is kept

 

 

*

detection time

<35>

 

 

 

shut off continuously.￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The main power off detection is invalid when you set up this to 1000.

 

 

6E

Emergency stop

0 to 500￿

%

 

You can set up the torque limit in case of emergency stop as below.￿

 

 

 

torque set up

<0>

 

 

 

• During deceleration with the setup of 8 or 9 of SV.Pr67 (Error response

 

 

 

 

 

 

 

 

at main power-off) ￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• During deceleration with the setup of 8 or 9 of SV.Pr69 (Sequence at

 

 

 

 

 

 

 

 

Servo-OFF) ￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Normal torque limit is used by setting this to 0.￿

 

 

 

 

 

 

 

 

 

 

 

<Caution>￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The stop is not due to the emergency stop input (EMG-STP: CN X5 Pin 2).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameters for Protective function

 

 

 

 

 

 

 

Standard default : < >

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Servo￿

Title

Setup￿

 

Unit

 

 

 

 

Function/Content

 

 

 

 

 

PrNo.

 

range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

Position deviation

0 to 32767

￿ 256 x

 

• You can set up the excess range of position deviation.

￿

 

 

 

error level

<25000>

 

pulse

 

• Set up with the encoder pulse counts at the position control and with the

 

 

 

 

 

 

 

 

external scale pulse counts at the full-closed control. ￿

 

 

 

 

 

 

 

 

 

 

• Err24 (Position deviation excess protection) becomes invalid when you

 

 

 

 

 

 

 

 

set up this to 0.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

72

Overload level

0 to 500￿

 

%

 

• You can set up the over-load level. The overload level becomes 115 [%]

 

 

 

 

<0>

 

 

 

by setting up this to 0. ￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Use this with 0 setup in normal operation. Set up other value only when

 

 

 

 

 

 

 

 

you need to lower the over-load level. ￿

 

 

 

 

 

 

 

 

 

 

 

 

• The setup value of this parameter is limited by 115[%] of the motor rating.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

71