Step Operation

Example of Rotary Axis Operation Setting

If the rotary axis operation is specified, the shaft moves in a direction nearest from the current position to a target position of a step parameter that the rotary axis operation (rotary) has been specified regarding 32.Pr03 (Movement per rotation in rotation coordinates) as 360 degrees.

A current position of running motor is automatically limited in a range between 0 and [travel per rotation at a rotary coordinate –1] as shown below.

• If travel per rotation at a rotary ￿

 

Origin = 0

 

 

 

 

coordinate is set to “10000”￿

... , 2, 1

9999, 9998, ...

 

 

 

Point 1 = 1250

 

 

Point 7 = 8750

 

 

 

 

 

 

 

 

 

 

 

 

 

Point 2 = 2500

 

 

 

 

Point 6 = 7500

 

 

 

 

 

 

Point 3 = 3750

 

 

Point 5 = 6250

 

 

 

 

 

 

 

Point 4 = 5000

 

 

 

 

• Setting of 32-bit positioning parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32.Pr**￿

Parameter name￿

Input value￿

 

 

 

 

 

03

 

Movement per rotation in rotation coordinates

 

10000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Setting of step parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.

 

 

Operation mode

Position/Waiting time

 

Speed

Acceleration

 

Deceleration

Block

01￿

 

Rotary axis operation (Rotary)￿

1250￿

 

 

VEL1￿

ACC1￿

 

DEC1￿

Single￿

 

 

 

 

 

 

 

 

 

 

 

02￿

 

Rotary axis operation (Rotary)￿

2500￿

 

 

VEL1￿

ACC1￿

 

DEC1￿

Single￿

 

 

 

 

 

 

 

 

 

 

 

03￿

 

Rotary axis operation (Rotary)￿

3750￿

 

 

VEL1￿

ACC1￿

 

DEC1￿

Single￿

 

 

 

 

 

 

 

 

 

 

 

04￿

 

Rotary axis operation (Rotary)￿

5000￿

 

 

VEL1￿

ACC1￿

 

DEC1￿

Single￿

 

 

 

 

 

 

 

 

 

 

 

05￿

 

Rotary axis operation (Rotary)￿

6250￿

 

 

VEL1￿

ACC1￿

 

DEC1￿

Single￿

 

 

 

 

 

 

 

 

 

 

 

06￿

 

Rotary axis operation (Rotary)￿

7500￿

 

 

VEL1￿

ACC1￿

 

DEC1￿

Single￿

 

 

 

 

 

 

 

 

 

 

 

07

 

Rotary axis operation (Rotary)

8750

 

 

VEL1

ACC1

 

DEC1

Single

 

 

 

 

 

 

 

 

 

 

 

 

 

Caution

1)Control mode

The rotary axis operation is enabled only for the position control (SV.Pr02 = 0). If the rotary axis operation is specified for the full-closed control (SV.Pr02 = 6), an error code No. 69 (undefined data error protection) is shown.

2)Restrictions on parameter

If the rotary axis operation is used, the restrictions below are imposed to the parameters not to exceed the limitation of the current position.

PrNo.￿

Name￿

Set value￿

Description￿

￿

￿

￿

The rotary axis operation requires homing. If “0” or “2” is

SV.Pr0B￿

Absolute encoder set up￿

1￿

set, an error code No. 69 (undefined data error protection)

￿

￿

￿

is shown when the rotary shaft operation starts.￿

16.Pr37￿

Home complete type￿

1￿

Be sure to set “1” if you use the home offset function.￿

16.Pr38￿

Homing skip￿

0￿

The rotary axis operation requires homing.￿

16.Pr54￿

Block operation type￿

0￿

The combined block operation cannot be used.￿

￿

￿

￿

For 16.Pr37 = 0, set “0”. For 16.Pr37 = 0, set a value in a

32.Pr00￿

Home offset￿

￿

range between 0 and [movement per rotation at a rotary

￿

￿

￿

coordinate - 1].￿

￿

￿

 

For any invalid value out of specified range, an error code

32.Pr03￿

Setting of maximum movement in plus

2 to￿

No. 69 (undefined data error protection) is shown when

￿

direction￿

1073741824 ￿

the positioning operation starts.￿

 

￿

32.Pr01￿

Setting of maximum movement in minus direction￿

0

A maximum travel limitation error protection cannot be

32.Pr02

Movement per rotation in rotation coordinates

 

used for the rotary axis operation.