System Configuration and Wiring

Overall Wiring (Connecting Example of E-frame)

• Wiring of the Main Circuit (see P.36, 37.)

(see P.32, 33 and 177.)

Circuit Breaker (NFB)￿

Use the circuit breaker matching capacity of the power source to protect the power lines.￿

￿

(see P.177 , 178.)

Noise Filter (NF)￿

Prevents external noise from the power lines. And reduces an effect of the noise generated by the servo driver. ￿

￿

(see P.32, 33.)

Magnetic Contactor (MC)￿

Turns on/off the main power of the servo driver.￿

Use a surge absorber together with this.￿

Never start nor stop the servo motor with this Magnetic Contactor. ￿

￿

(see P.189.)

Reactor (L)￿

Reduces harmonic current of the main power.

Pin P, B1 and B2...￿

B1 and B2 to be kept shorted for nor-

mal operation. ￿

￿

When the capacity shortage of the regenerative resister is found, dis- connect a short bar between B1 and B2, then connect the external regenerative resister between P and B2.￿

Install an external regenerative re- sister on incombustible material, such as metal. Follow the same wir-

ing connection as the above. ￿

￿

When you connect an external re- generative resister, set up SV.Pr6C to 1 or 2.

Connection with input ￿ power supply￿

<Remarks>￿

Before turning the power ￿ supply on, check whether ￿ the input voltage is correct.

L1

L2

L3

r

t

Connection to external components

P

B2

Ground (earth)

Regenerative resistor (optional)￿ <Remarks>￿

When you use an external regenerative resister, install an external protective apparatus, such as thermal fuse without fail.￿

Thermal fuse and thermostat are built in to the regenerative resistor (Option). If the thermal fuse is activated, it will not resume.

30

Page 30
Image 30
Panasonic A4P Series Overall Wiring Connecting Example of E-frame, Pin P, B1 and B2, Connection to external components