Parameter Setup

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard default : < >

Servo￿

Title

Setup￿

Unit

 

 

 

 

Function/Content

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PrNo.

 

range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

69

Sequence at ￿

0 to 9￿

–￿

You can set up,￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Servo-OFF

<0>

 

 

1) the running condition during deceleration and after stalling￿

 

 

 

 

 

 

 

 

 

 

 

 

2) the clear treatment of deviation counter is set up. ￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

After the servo-ON signal input is turned off (SRV-ON : CN X5, Pin-23

 

 

 

 

 

shifting from ON to OFF).￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The relation between the setup value of SV.Pr69 and the action/deviation

 

 

 

 

 

counter clearance is same as that of SV.Pr67 (Error response at main

 

 

 

 

 

power-off).￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to P.135, "Timing Chart"-Servo-ON/OFF action while the motor is at

 

 

 

 

 

stall" of Operation Setting as well.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6A

Mechanical brake

0 to 100￿

2ms

You can set up the time from when the brake release signal (BRK-OFF :

 

 

delay at motor

<0>

 

CN X5, Pin-10 and 11) turns off to

when the motor is de-energized

 

 

standstill

 

 

(Servo-free), when the motor turns to Servo-OFF while the motor is at

 

 

 

 

stall.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set up to prevent a

micro-travel/

SRV-ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

drop of the motor (work) due to the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BRK-OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

action delay time (tb) of the brake￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

release

 

 

tb

 

 

 

hold

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

After setting up SV.Pr6a >= tb

, ￿

actual brake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

then compose the sequence

so as

 

release

 

 

 

 

 

 

 

hold

 

 

 

 

 

 

 

 

the driver turns to Servo-OFF after

motor￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the brake is actually activated.

 

 

energized

 

 

 

 

 

 

 

non-￿

 

 

 

 

 

 

 

 

 

energization

 

 

 

 

 

 

 

energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pr6A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to P.135, "Timing Chart"-Servo-ON/OFF Action While the Motor Is

 

 

 

 

 

at Stall" of Operation Setting as well.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6B

Mechanical brake

0 to 100￿

2ms

You can set up time from when detecting the off of Servo-ON input signal

 

 

delay at motor in

<0>

 

(SRV-ON : CN X5, Pin-29) is to when external brake release signal

 

 

motion

 

 

(BRK-OFF : CN X5, Pin-10 and 11) turns off, while the motor turns to

 

 

 

 

servo off during the motor in motion.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set up to

prevent

the

brake

SRV-ON

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

 

 

 

 

 

 

 

 

 

OFF

 

 

 

 

 

 

 

 

deterioration

due to

the

motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BRK-OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

running.￿

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

release

 

 

 

 

 

 

 

hold

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• At Servo-OFF during the motor is

actual￿

 

 

 

 

 

tb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

running, tb of the right fig. will be

energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

brake

 

 

 

 

 

 

 

 

 

non-￿

 

 

 

 

 

 

 

 

a shorter one of either SV.Pr6B

 

 

 

 

 

 

 

 

 

 

 

 

 

energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setup time, or time lapse till the

motor￿

 

 

 

 

 

 

 

 

 

 

 

 

30 r/min

 

 

 

 

 

 

 

 

motor speed falls below 30r/min.

energization

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refer to P.135, "Timing Chart"-Servo-ON/OFF action while the motor is in

 

 

 

 

 

motion" of Operation Setting as well.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

<Notes>

For servo parameters which No. have a suffix of "*", changed contents will be validated when you turn on the control power.