INSTALLATION

A-6

 

 

 

Do not cross the welding cables at the output terminal connection. Keep the cables isolated and separate from one another.

------------------------------------------------------------------------

AUXILIARY POWER RECEPTACLES

The auxiliary power of the RANGER 305G consists of two 20 Amp-120 VAC (5-20R) duplex receptacles and one 50 Amp 120/240 VAC (14-50R) receptacle. The 240 VAC receptacle can be split for single phase 120 VAC operation.

The auxiliary power capacity is 9,000 watts of 60 Hz, single phase power. The auxiliary power capacity rat- ing in watts is equivalent to volt-amperes at unity power factor. The max permissible current of the 240 VAC output is 38 Amps. The 240 VAC output can be split to provide two separate 120 VAC outputs with a max permissible current of 38 Amps per output to two separate 120 VAC branch circuits (these circuits can- not be paralleled). Output voltage is within ± 10% at all loads up to rated capacity.

The 120 V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the current capacity of the associated receptacle.

NOTE: The 240 V receptacle has two 120 V circuits, but are of opposite polarities and cannot be paralleled.

STANDBY POWER CONNECTIONS

The RANGER 305G is suitable for temporary, standby or emergency power using the engine manufacturer’s recommended maintenance schedule.

The RANGER 305G can be permanently installed as a standby power unit for 240 VAC, 3 wire, single phase, 38 amp service. Connections must be made by a licensed electrician who can determine how the 120/240 VAC power can be adapted to the particular installation and comply with all applicable electrical codes.

Install the double-pole, double-throw switch between the power company meter and the premis- es disconnect. Switch rating must be the same or greater than the customer’s premises disconnect and service over current protection.

Take necessary steps to assure load is limited to the capacity of the RANGER 305G by installing a 40 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 38 amperes. Loading above the rated output will reduce output voltage below the allow- able - 10% of rated voltage which may damage appliances or other motor-driven equipment and may result in overheating of the RANGER 305G engine and/or alternator windings.

Install a 50 amp, 120/240 VAC plug (NEMA Type 14-50) to the double-pole circuit breaker using No. 6, 4 conductor cable of the desired length. (The 50 amp, 120/240 VAC plug is available in the optional K802R plug kit or as part number T12153-9.)

Plug this cable into the 50 Amp, 120/240 Volt recep- tacle on the RANGER 305G case front.

RANGER 305G

Image 14
Contents Safety Depends on You Ranger 305 GSafety Electric Shock can kill Cylinder may explode if damaged Précautions DE Sûreté Thank You Table of Contents Vii Installation Machine Specifications Ranger 305G K1726-1 Safety Precautions PRE-OPERATION Engine Service Electrical Connections Auxiliary Power Receptacles Connection of Ranger 305G to Premises Wiring Connection of Lincoln Electric Wire Feeders Connection of an LN-23P Wire Feeder to the Ranger 305GEngine Operation Safety PrecautionsFor Auxiliary Power ADD FuelDigital Output Meters Weld Mode Selector SwitchWelding Controls ARC ControlWeld Output Terminals with Flange NUT Weld Terminals Control SwitchWire Feeder Voltmeter Switch PIN AmphenolTypical Ranger 305G Fuel Consumption StoppingWelder Operation TIG Welding Wire WELDING-CVTypical Current Ranges 1 for Tungsten ELECTRODES2 Ranger 305G Extension Cord Length Recommendations Auxiliary PowerARC Gouging Accessories T12153-9 50 AMP, 120/240 V Power PlugKohler CH22 Engine FrequencyMake and Part Number Air Pre-cleaner Service Engine Oil Refill Capacities Without oil filter replacementAir Cleaner Service Engine Oil ChangeSpark Plug AIR Filter Paper ElementOverspeed is Hazardous Cleaning the BatteryCharging the Battery Checking the Electrolyte LevelWelder/Generator Maintenance Troubleshooting Is Evident.Authorized Field Service Facility Contact your local Lincoln Authorized Field Service FacilityWelding without a control cable Authorized Field Service Facility Contact your local LincolnStick Diagrams Diagrams Diagrams Diagrams Diagrams Engine Welders /LN-8 Connection Diagram S24787-6Diagrams Diagrams Diagrams Diagrams Diagrams G3743 23.50 16.75Ranger 305G Precaucion Warnung