Friedrich CP14N10 manual Refrigeration System Sequence of Operation, Refrigerant System Components

Page 8

Refrigeration System Sequence of Operation

A good understanding of the basic operation of the refrigera- tion system is essential for the service technician. Without this understanding, accurate troubleshooting of refrigeration system problems will be more difficult and time consuming, if not (in some cases) entirely impossible. The refrigeration system uses four basic principles (laws) in its operation they are as follows:

1.“Heat always flows from a warmer body to a cooler body.”

2.“Heat must be added to or removed from a substance before a change in state can occur”

3.“Flow is always from a higher pressure area to a lower pressure area.”

4.“The temperature at which a liquid or gas changes state is dependent upon the pressure.”

The refrigeration cycle begins at the compressor. Starting the compressor creates a low pressure in the suction line which draws refrigerant gas (vapor) into the compressor. The compressor then “compresses” this refrigerant, raising its pressure and its (heat intensity) Temperature.

The refrigerant leaves the compressor through the discharge line as a hot high pressure gas (vapor). The refrigerant enters the condenser coil where it gives up some of its heat. The condenser fan moving air across the coil’s finned surface facilitates the transfer of heat from the refrigerant to the relatively cooler outdoor air.

When a sufficient quantity of heat has been removed from the refrigerant gas (vapor), the refrigerant will “condense” (i.e. change to a liquid). Once the refrigerant has been condensed (changed) to a liquid it is cooled even further by the air that continues to flow across the condenser coil.

The RAC design determines at exactly what point (in the condenser) the change of state (i.e. gas to a liquid) takes place. In all cases, however, the refrigerant must be totally condensed (changed) to a liquid before leaving the condenser coil.

The refrigerant leaves the condenser coil through the liquid line as a warm high pressure liquid. It next will pass through the refrigerant drier (if so equipped). It is the function of the drier to trap any moisture present in the system, contaminants, and large particulate matter.

The liquid refrigerant next enters the metering device. The metering device is a capillary tube. The purpose of the metering device is to “meter” (i.e. control or measure) the quantity of refrigerant entering the evaporator coil.

In the case of the capillary tube this is accomplished (by design) through size (and length) of device, and the pressure difference present across the device.

Since the evaporator coil is under a lower pressure (due to the suction created by the compressor) than the liquid line, the liquid refrigerant leaves the metering device entering the evaporator coil. As it enters the evaporator coil, the larger area and lower pressure allows the refrigerant to expand and lower its temperature (heat intensity). This expansion is often referred to as “boiling”. Since the unit’s blower is moving Indoor air across the finned surface of the evaporator coil, the expanding refrigerant absorbs some of that heat. This results in a lowering of the indoor air temperature, hence the “cooling” effect.

The expansion and absorbing of heat cause the liquid refrigerant to evaporate (i.e. change to a gas). Once the refrigerant has been evaporated (changed to a gas), it is heated even further by the air that continues to flow across the evaporator coil.

The particular system design determines at exactly what point (in the evaporator) the change of state (i.e. liquid to a gas) takes place. In all cases, however, the refrigerant must be totally evaporated (changed) to a gas before leaving the evaporator coil.

The low pressure (suction) created by the compressor causes the refrigerant to leave the evaporator through the suction line as a cool low pressure vapor. The refrigerant then returns to the compressor, where the cycle is repeated.

Refrigerant System Components

Suction

Discharge

Line

Line

Evaporator

Condenser

Coil

Coil

 

Compressor

Metering

Refrigerant Drier

Device

Liquid

Refrigerant

Line

Dryer

 

8

Image 8
Contents Service & Parts Manual Table of Contents Specifications and Technical Parameters Performance DataOuter Component Identification Models CP14N10, CP18N30, CP24N30Installation Dimensions Wiring Diagrams Functional Component Definitions Mechanical ComponentsRefrigeration System Sequence of Operation Refrigerant System ComponentsSealed Refrigeration System Repairs Equipment RequiredRefrigerant Charging Method of ChargingUndercharged Refrigerant Systems Restricted Refrigerant System Cooling Only Room Air Conditioners Troubleshooting Tips Problem Possible Cause ActionReplace fuse, reset breaker. If repeats, check fuse Overload inoperative. Opens too soon Surfaces Heat / Cool Room Air Conditioners Troubleshooting Tips Switch unit several times from heating to cooling Components Model CP14N10 No Description Qty Friedrich Part# CodeModel CP14N10 Models CP18C30 & CP18N30 Description Qty Friedrich Part# CodeFront Clapboard of Snail Shell Model CP24N30 Model CP24N30 Model CP24N30 Room AIR Conditioners Limited Warranty CP-14-18-24-Svc-Prts-07
Related manuals
Manual 28 pages 21.43 Kb

CP14N10, CP18N30, CP24N30 specifications

The Friedrich CP24N30, CP18N30, and CP14N10 are a trio of innovative portable air conditioning units designed to provide optimal comfort in residential and commercial settings. Each model boasts distinct features tailored to various room sizes, ensuring efficient temperature management.

Starting with the Friedrich CP24N30, this unit is engineered for larger spaces, able to cool areas up to 1,500 square feet. Its powerful cooling capacity of 24,000 BTUs allows it to quickly lower temperatures even in challenging environments. This model incorporates advanced inverter technology, which enhances energy efficiency by adjusting its cooling output according to the current temperature. Furthermore, the CP24N30 is equipped with a robust dehumidification function, capable of removing excess moisture from the air, making it ideal for humid climates. Its user-friendly interface, remote control, and Wi-Fi capability allow for convenient operation from anywhere in the home.

The Friedrich CP18N30 is a versatile choice for medium-sized rooms, covering up to 1,100 square feet with its 18,000 BTU cooling capacity. Like its larger counterpart, it features inverter technology, which not only saves energy but also results in quieter operation, a crucial factor for those who prioritize peace and tranquility in their living spaces. The CP18N30 also has a high EER (Energy Efficiency Ratio), making it a cost-effective option for cooling. Its built-in timer, along with programmable settings, enables homeowners to schedule operation according to their lifestyle, ensuring cooling is available when it is most required.

Lastly, the Friedrich CP14N10 is designed for smaller rooms, offering a cooling capacity of 14,000 BTUs and catering to areas up to 600 square feet. This unit balances performance and size, making it an excellent option for apartments and smaller living spaces. The CP14N10 maintains the brand's commitment to efficiency with its inverter technology that minimizes energy usage while maximizing cooling output. Like the other models, it includes a dehumidification setting, enhancing indoor air quality by alleviating humidity levels.

In all three models, Friedrich integrates smart technologies such as fault diagnosis and self-cleaning capabilities, ensuring reliability and ease of maintenance. Additionally, they come equipped with washable filters, promoting long-term efficiency and cleaner air. With their varying cooling capacities, these units offer tailored solutions for a wide array of environments while emphasizing energy efficiency and user convenience.