Heat / Cool Room Air Conditioners: Troubleshooting Tips

Problem

Possible Cause

Action

 

Heat anticipator (resistor) shorted (on applicable

Disconnect power to unit. Remove resistor from t-

 

stat bulb block. Plus in unit & allow to operate. Feel

 

models)

 

resistor for heat. If not heat, replace resistor

Room temperature

 

 

 

uneven

Wide differential - partial loss of t-stat bulb charge

Replace t-stat & check

(Heating cycle)

 

 

 

 

 

 

Incorrect wiring

Refer to appropriate wiring diagram. Resistor is

 

energized during "ON" cycle of compressor or fan.

 

 

 

 

 

Problem

Possible Cause

Action

 

Incorrect wiring

Refer to appropriate wiring diagram

 

Defrost control timer motor not advancing

Check for voltage at "TM" & "TM1" on timer. If no

 

(applicable models)

voltage, replace control

 

 

If outside coil temperature is 25F or below, &

 

Defrost control out of calibration (applicable models)

preselected time limit has elapsed, replace defrost

Unit will not defrost

 

control

 

 

If contacts remain closed between terminals "2"

 

Defrost control contacts stuck

& "3" of the defrost control after preselected time

 

 

interval has passed, replace control

 

Defrost control bulb removed from or not making

Reinstall & be assured that good bulb to coil contact

 

good coil contact

is made

Problem

Possible Cause

Action

 

Exhaust or fresh air door open

Check if operating properly. Instruct customer on

 

proper use of control

 

 

 

Dirty filter

Clean as recommended in Owner's Manual

 

 

Check heat rise across coil. If unit operates

 

Unit undersized

efficiently, check if insulation can be added to attic

 

or walls. If insulation is adequate, recommend

 

 

Does not heat

 

additional unit or larger one

 

 

adequately

Outdoor t-stat open (applicable models)

T-stat should close at 38°F. Check continuity of

 

 

control. If temperature is below 38°F, replace control

 

 

 

 

 

 

Heater hi-limit control cycling on & off

Check for adequate fan air across heater. Check

 

control for open at 160°F & close at 150°F

 

 

 

Shorted supplementary heater

Ohmmeter check, approx. 32-35 ohms

 

Incorrect wiring

Check applicable wiring diagram

17

Image 17
Contents Service & Parts Manual Table of Contents Performance Data Specifications and Technical ParametersModels CP14N10, CP18N30, CP24N30 Outer Component IdentificationInstallation Dimensions Wiring Diagrams Mechanical Components Functional Component DefinitionsRefrigerant System Components Refrigeration System Sequence of OperationEquipment Required Sealed Refrigeration System RepairsMethod of Charging Refrigerant ChargingUndercharged Refrigerant Systems Restricted Refrigerant System Problem Possible Cause Action Cooling Only Room Air Conditioners Troubleshooting TipsReplace fuse, reset breaker. If repeats, check fuse Overload inoperative. Opens too soon Surfaces Heat / Cool Room Air Conditioners Troubleshooting Tips Switch unit several times from heating to cooling Components No Description Qty Friedrich Part# Code Model CP14N10Model CP14N10 Description Qty Friedrich Part# Code Models CP18C30 & CP18N30Front Clapboard of Snail Shell Model CP24N30 Model CP24N30 Model CP24N30 Room AIR Conditioners Limited Warranty CP-14-18-24-Svc-Prts-07
Related manuals
Manual 28 pages 21.43 Kb

CP14N10, CP18N30, CP24N30 specifications

The Friedrich CP24N30, CP18N30, and CP14N10 are a trio of innovative portable air conditioning units designed to provide optimal comfort in residential and commercial settings. Each model boasts distinct features tailored to various room sizes, ensuring efficient temperature management.

Starting with the Friedrich CP24N30, this unit is engineered for larger spaces, able to cool areas up to 1,500 square feet. Its powerful cooling capacity of 24,000 BTUs allows it to quickly lower temperatures even in challenging environments. This model incorporates advanced inverter technology, which enhances energy efficiency by adjusting its cooling output according to the current temperature. Furthermore, the CP24N30 is equipped with a robust dehumidification function, capable of removing excess moisture from the air, making it ideal for humid climates. Its user-friendly interface, remote control, and Wi-Fi capability allow for convenient operation from anywhere in the home.

The Friedrich CP18N30 is a versatile choice for medium-sized rooms, covering up to 1,100 square feet with its 18,000 BTU cooling capacity. Like its larger counterpart, it features inverter technology, which not only saves energy but also results in quieter operation, a crucial factor for those who prioritize peace and tranquility in their living spaces. The CP18N30 also has a high EER (Energy Efficiency Ratio), making it a cost-effective option for cooling. Its built-in timer, along with programmable settings, enables homeowners to schedule operation according to their lifestyle, ensuring cooling is available when it is most required.

Lastly, the Friedrich CP14N10 is designed for smaller rooms, offering a cooling capacity of 14,000 BTUs and catering to areas up to 600 square feet. This unit balances performance and size, making it an excellent option for apartments and smaller living spaces. The CP14N10 maintains the brand's commitment to efficiency with its inverter technology that minimizes energy usage while maximizing cooling output. Like the other models, it includes a dehumidification setting, enhancing indoor air quality by alleviating humidity levels.

In all three models, Friedrich integrates smart technologies such as fault diagnosis and self-cleaning capabilities, ensuring reliability and ease of maintenance. Additionally, they come equipped with washable filters, promoting long-term efficiency and cleaner air. With their varying cooling capacities, these units offer tailored solutions for a wide array of environments while emphasizing energy efficiency and user convenience.