6F3B0253
10.Troubleshooting
10.1Troubleshooting procedure
! | CAUTION | 1. Pay special attention during the troubleshooting to minimize the risk of | |
electrical shock. | |||
|
|
2.Turn off power immediately if the
3.Turn off power before removing or replacing units, modules, terminal blocks or wires. Failure to do so can cause electrical shock or damage to the T1 and related equipment.
4.Contact Toshiba for repairing if the
If a trouble occurs, determine whether the cause lies in the mechanical side or in the control system (PLC) side. A problem may cause a secondary problem, therefore, try to determine the cause of trouble by considering the whole system.
If the problem is found in the
PWR (power) LED
Lit
RUN LED
Lit
User program
Normal operation
Input operation
Normal operation
Output operation
|
| Follow the procedure in |
| Not lit | |
| 10.1.1 Power supply check | |
| ||
|
| Follow the procedure in |
|
| |
| Not lit | |
| 10.1.2 CPU check | |
| ||
|
| |
|
| Follow the procedure in |
|
| |
| Not normal | |
| 10.1.3 Program check | |
| ||
| Not normal | Follow the procedure in |
| 10.1.4 Input check | |
| Not normal | Follow the procedure in |
| 10.1.5 Output check | |
|
|
Also refer to section 10.1.6 for environmental problem.
282