6F3B0253
Basic Hardware and Function 189
7. Instructions
FUN 107 D<= Double-word less than or equal
Expression
Input [ A+1A D<= B+1B ] Output
Function
When the input is ON, the double-word data of A+1A and B+1B are compared, and if A+1A is
less than or equal to B+1B, the output is turned ON.
Execution condition
Input Operation Output
OFF No execution OFF
ON Execution A+1A B+1BON
A+1A > B+1BOFF
Operand
Name Device Register Constant Index
X Y R S T. C. XWYWRWSW T C D I J K
ACompared
data √√√√√√√ √
BReference
data √√√√√√√ √
Example
When R010 is ON, the data of D0101D0100 is compared with the constant data 0, and if the
data of D0101D0100 is less than or equal to 0, R014 is turned ON.
If the data of D0101D0100 is -1, R014 is turned ON.
D0101D0100 -1 Constant 0 R014 is ON
If the data of D0101D0100 is 10000, R014 is turned OFF.
D0101D0100 10000 >Constant 0 R014 is OFF
Note
This instruction deals with the data as double-word integer (-2147483648 to 2147483647).