6F3B0253
196 T1-16S User’s Manual
7. Instructions

FUN 114 SET Device/register set

Expression
Input [ SET A ] Output
Function
When the input is ON, the device A is set to ON if A is a device, or the data HFFFF is stored in the
register A if A is a register.
Execution condition
Input Operation Output
OFF No execution OFF
ON Execution ON
Operand
Name Device Register Constant Index
X Y R S T. C. XWYWRWSW T C D I J K
ADevice or
register √√√ √√√√√√√√√
Example 1 (device set)
When R010 is ON, R025 is set to ON. The state of R025 is remained even if R010 comes
OFF.
Example 2 (register set)
When R010 is ON, the data HFFFF is stored in RW20. (R200 to R20F are set to ON)
The state of RW20 is remained even if R010 comes OFF.