6F3B0253

7. Instructions

< Write command mode (Mode 3) >

When the instruction input comes ON with the operand B+1 is 3, the Write command mode (mode 3) is selected. In this mode, the T1-16S sends the user specified Write command to the Inverter specified by the operand B, and repeats.

Repeat

Sends the specified command with command data to #n Inverter

Checks the acknowledge

The target Inverter number #n is specified by the operand B.

The scan execution status and the Inverter communication status are stored in the operand B+2 to B+7.

The command code and the command data setting registers are indirectly specified by the operand A and A+1.

When the instruction input is reset to OFF, the operation is stopped after receiving the response from the Inverter.

Example

D1000

D1001

Data table designation

4RW200

3010RW201 RW202 RW203 RW204 RW205 RW206 RW207

Parameter & status

5

3 (mode 3)

Execution status

Comm error code

Inverter comms

status map

D1010

D1011

RS-485 port

H0030 (fixed)

0 (fixed)

When the data for each operand are set as above, the following operation condition is specified.

RW200=5 The target Inverter number is 5. Therefore T1-16S communicates with #5 Inverter.

D1000=4 & D1001=3010 D3010 is specified as the command code setting register and D3011 is specified as the command data setting register.

Data table:

Register

D3010

D3011

Data contents

Command code

Command data

Signal direction

Write

Example operation:

For example, to write the acceleration time parameter (10 seconds) to the #5 Inverter, set the command code H0009 into D3010 and the value 100 into D3011.

For the command code and the command data format, refer to your Inverter manual.

252 T1-16S User’s Manual

Page 254
Image 254