10.Troubleshooting
10.1.2CPU check
If the PWR (power) LED is lit but the RUN LED is not lit, check the following points.
Check the position of the mode control switch
Check the FLT (fault) LED
programming
Is the RUN LED blinking ?
whether the not used.
Connect the programming tool, and check the
If it is not in R (RUN) position, turn the switch to R (RUN) position.
If the FLT LED is lit or blinking, the
message by connecting the tool. Refer to section 10.2.
If it is blinking, the
HOLD device (S401) is
If the
If the communication between the
10.1.3Program check
Check the user program based on the following points if it is running but the operation does not work as intended.
(1)Whether duplicated coils are not programmed.
(2)Whether a coil device and a destination of a function instruction are not overlapping.
(3)Whether the ON/OFF duration of an external input signal is not shorter than the
(4)Whether a register/device, which is used in the main program, is not operated erroneously in the interrupt program.
NOTE
When you write/modify the program, it is necessary to execute the EEPROM write operation before turning off power to the T1. Otherwise the old program stored in the