214 T1-16S User’s Manual
7. Instructions
FUN 146 STOT Step sequence output
Expression
Input −[ STOT A ]−
Function
When the input is ON, the device A is set to ON and the devices of STIN instructions on the same
rung are reset to OFF.
Execution condition
Input Operation Output
OFF No execution -
ON Execution -
Operand
Name Device Register Constant Index
X Y R S T. C. XWYWRWSW T C D I J K
AStep device √
Example
See example on STIN (FUN 145) instruction.
Note
• The STIZ, STIN and STOT instructions are used together to configure the step sequence.
• Two or more STOT instructions can be placed on one rung to perform simultaneous sequences.
• Two or more STIN instructions can be placed on one rung in parallel or in series to perform loop
or convergence of sequences. (Max. 11 STIN instructions on one rung)
• To perform the conditional branch (sequence selection), separate the rungs as follows.
This limitation is applied to T1 version 1.00 only.
[ STIN A ] | | [ STOT B ] [ STIN A ] | | [ STOT B ]
| | [ STOT C ] [ STIN A ] | | [ STOT C ]
Not allowed Available