6F3B0253
216 T1-16S User’s Manual
7. Instructions

FUN 149 U/D Up-down counter

Expression
Direction input U U/D Q Output
Count input C
Enable input E A
Function
While the enable input is ON, this instruction counts the number of the count input changes from
OFF to ON. The count direction (up count or down count) is selected by the state of the direction
input. The count value is stored in the counter register A. The count value range is 0 to 65535.
Up count when the direction input is ON
Down count when the direction input is OFF
When the enable input is OFF, the counter register A is cleared to 0.
Execution condition
Enable
input Operation Output
OFF No operatio n (A is cleared to 0) OFF
ON Count v alue is not limit val ue (0 or 65535) OFF
Count value is limit value and count input is ON ON
Operand
Name Device Register Constant Index
X Y R S T. C. XWYWRWSW T C D I J K
ACount value
Example
X005
X006
R010
C005
C.005
Note
The transitional contact is required for
the count input. Otherwise, counting is
executed every scan during X005 is ON
in this example.
For the direction input and the count
input, direct linking to a connecting point
is not allowed. Refer to Note of Shift
register FUN 074.