6F3B0253
38 T1-16S User’s Manual
2. Specifications

2.1 General specifications

Item T1-16S
Power supply voltage 100 to 240Vac (+10/-15%), 50/60 Hz
Power consump tion 45VA or less
Inrush current 50A or less (at 240Vac, cold start)
24Vdc
(24Vdc, ±10%)
0.2A (for external dev ices and/or for input signals)
AC Power type
Output
rating
(Note) 5Vdc 1.5A (for I/O module)
Power supply voltage 24Vdc (+20/-15%)
Power consumption 18W or l ess
Inrush current 25A or less (at 24Vdc)
DC Power type
5Vdc output rating (Note) 1.5A (for I/O module)
Retentive power interrup tion 10ms or less
Insulation resistance 10M or more
(between power terminals and ground terminal)
Withstand volt age 1500Vac - 1 minute
Ambient temperature 0 to 55°C (operation), -20 to 75°C (storage)
Ambient humidity 5 to 95%RH, no condensation
Noise immunity 1000Vp-p/1µs, Conform to EMC Directive 89/336/EEC
Vibration immunit y 9.8m/s2 (1g)
(for 30 minutes p er axis, on 3 mutually perpendicular axes)
Shock immunity 98m/s2 (10g)
(3 shocks p er axis, on 3 mutual ly perpendicular axes)
Approximate weight 500g

(1) 24Vdc service power output is not provided on the DC power supply type.

(2) The maximum output current of the 5Vdc is 1.5A. However there is the following

restrictions, depending on the conditions.

When HP911 is used:

Redused by 0.2A

When RS-485 port is used:

Reduced by 0.1A

When 24Vdc service power is used:

Refer to the right chart.

NOTE
24Vdc service power
5Vdc
maximum load current
0.2 (A)0.1
1.5
(A)
1.0