6F3B0253
Basic Hardware and Function 245
7. Instructions
FUN 236 XFER Expanded data transfer (Inverter connection mode)
Expression
Input [ A XFER B C ] Output
Function
This function is provided to control Toshiba Inverters VF-A7/G7/S9 connected on the RS-485 line.
When the RS-485 port operation mode is set to the Inverter mode (SW56 = 3), the T1-16S can
perform the following functions for up to 63 Inverters.
(1) Cyclically scans the Inverters and sends/receives the following data to/from each Inverter.
Send to Inverter: Frequency reference write and Operation command write (Run, Stop, etc.)
Receive from Inverter: Operating frequency monitor and Output terminal status monitor
(2) Cyclically scans the Inverters and receives the following data from each Inverter.
Receive from Inverter: Operating frequency monitor and Output terminal status monitor
(3) Sends a specified Read command to a specified Inverter and stores the response data.
(4) Sends a specified Write command with the command data to a specified Inverter.
(5) Sends a specified Write command with the command data to all the connected inverters as
broadcast.
Execution condition
Input Operation O utput ERF
OFF No execution OFF
ON Norm al execution ON
When error is occurred (see Note) ON Set
Operand
Name Device Register Constant Index
X Y R S T. C. XWYWRWSW T C D I J K
AData table √√√√√√√
BInverter No. √√√√√√√
CRS-485 port √√√√√√

Parameters

Data table designation Parameter and status RS-485 port designation
ARegister type code BInv erter number CFixed to H0030
A+1 Leading address B+1 O peration mode C+1 Fixed to 0
B+2 Execution status
B+3 Communication error code
B+4 Inverter communi cation
B+5 status map
B+6 (each bit shows each
B+7 Inverter status)
Data table designation (A, A+1):
Register Type code (A) Leading address ( A+1)
RW register H0003 0 to 255
D register H0004 0 to 4095