7. Instructions
FUN 236
XFER
Expanded data transfer (Inverter connection mode)
Expression
Input − [ A XFER B → C ]− Output
Function
This function is provided to control Toshiba Inverters
(1)Cyclically scans the Inverters and sends/receives the following data to/from each Inverter.
•Send to Inverter: Frequency reference write and Operation command write (Run, Stop, etc.)
•Receive from Inverter: Operating frequency monitor and Output terminal status monitor
(2)Cyclically scans the Inverters and receives the following data from each Inverter.
•Receive from Inverter: Operating frequency monitor and Output terminal status monitor
(3)Sends a specified Read command to a specified Inverter and stores the response data.
(4)Sends a specified Write command with the command data to a specified Inverter.
(5)Sends a specified Write command with the command data to all the connected inverters as broadcast.
Execution condition
Input | Operation | Output | ERF |
OFF | No execution | OFF | − |
ON | Normal execution | ON | − |
| When error is occurred (see Note) | ON | Set |
Operand
| Name |
|
| Device |
|
|
|
|
|
|
|
|
| Register |
|
| Constant | Index | ||||
|
| X | Y | R | S | T. | C. | XW | YW | RW | SW | T | C | D | I | J | K |
|
| |||
A | Data table |
|
|
|
|
|
| √ | √ |
| √ | √ |
| √ | √ | √ |
|
|
|
|
|
|
B | Inverter No. |
|
|
|
|
|
| √ | √ |
| √ | √ |
| √ | √ | √ |
|
|
|
|
|
|
C |
|
|
|
|
|
|
|
| √ |
| √ | √ | √ | √ | √ |
|
|
|
|
|
|
Parameters
Data table designation
ARegister type code
A+1 Leading address
B B+1 B+2 B+3 B+4 B+5 B+6 B+7
Parameter and status
Inverter number
Operation mode
Execution status
Communication error code
Inverter communication
status map
(each bit shows each
Inverter status)
C C+1
Fixed to H0030
Fixed to 0
Data table designation (A, A+1):
Register | Type code (A) | Leading address (A+1) |
RW register | H0003 | 0 to 255 |
D register | H0004 | 0 to 4095 |