6F3B0253
Basic Hardware and Function 247
7. Instructions
< Data exchange mode (Mode 0) >
When the instruction input comes ON with the operand B+1 is 0, the Data exchange mode
(mode 0) is selected. In this mode, the T1-16S sends the following commands to the Inverters
starting from #0 through the Inverter number specified by the operand B, and repeats.
#0 Frequency reference write (FA01)
#0 Operation command write (FA00)
#1 Frequency reference write (FA01)
#1 Operation command write (FA00)
:
#n Frequency reference write (FA01)
#n Operation command write (FA00)
#0 Operating frequency monitor (FD00 )
#0 Output terminal status monitor (F E0 7 )
#1 Operating frequency monitor (FD00 )
#1 Output terminal status monitor (F E0 7 )
:
#n Operating frequency monitor (FD00 )
#n Output terminal status monitor (F E0 7 )
The maximum Inverter number #n is specified by the operand B.
The scan execution status and the Inverter communication status are stored in the operand
B+2 to B+7.
The command data table is specified by the operand A and A+1.
When the instruction input is reset to OFF, the operation is stopped after receiving the
response from the Inverter currently communicating.
Example
Data table designation Parameter & status RS-485 port
D1000 4 RW200 5 D1010 H0030 (f ixed)
D1001 2000 RW201 0 (mode 0) D1011 0 (fixed)
RW202 Execution stat us
RW203 Comm error code
RW204
RW205 Inverter com ms
RW206 status m ap
RW207
When the data for each operand are set as above, the following operati on condition is specified.
RW200=5 The max Inverter number is 5. Therefore T1-16S scans from #0 through #5 Inverters.
D1000=4 & D1001=2000 D2000 is specified as the data table starting address.
Scan