6F3B0253

7. Instructions

< Data exchange mode (Mode 0) >

When the instruction input comes ON with the operand B+1 is 0, the Data exchange mode (mode 0) is selected. In this mode, the T1-16S sends the following commands to the Inverters starting from #0 through the Inverter number specified by the operand B, and repeats.

 

#0 Frequency reference write (FA01)

 

#0 Operation command write (FA00)

 

#1 Frequency reference write (FA01)

 

#1 Operation command write (FA00)

 

:

 

Scan

#n

Frequency reference write (FA01)

#n

Operation command write (FA00)

 

#0 Operating frequency monitor (FD00)

 

#0 Output terminal status monitor (FE07)

 

#1 Operating frequency monitor (FD00)

 

#1 Output terminal status monitor (FE07)

 

:

 

 

#n

Operating frequency monitor (FD00)

 

#n

Output terminal status monitor (FE07)

The maximum Inverter number #n is specified by the operand B.

The scan execution status and the Inverter communication status are stored in the operand B+2 to B+7.

The command data table is specified by the operand A and A+1.

When the instruction input is reset to OFF, the operation is stopped after receiving the response from the Inverter currently communicating.

Example

D1000

D1001

Data table designation

4RW200

2000RW201 RW202 RW203 RW204 RW205 RW206 RW207

Parameter & status

5

0 (mode 0)

Execution status

Comm error code

Inverter comms

status map

D1010

D1011

RS-485 port

H0030 (fixed)

0 (fixed)

When the data for each operand are set as above, the following operation condition is specified.

RW200=5 The max Inverter number is 5. Therefore T1-16S scans from #0 through #5 Inverters.

D1000=4 & D1001=2000 D2000 is specified as the data table starting address.

Basic Hardware and Function 247

Page 249
Image 249
Toshiba 6F3B0253 user manual Data exchange mode Mode, Example