6F3B0253

7. Instructions

FUN 096

>

Greater than

Expression

Input [ A > B ]Output

Function

When the input is ON, the data of A and the data of B are compared, and if A is greater than B, the output is turned ON.

Execution condition

Input

 

 

 

Operation

Output

OFF

No execution

 

 

 

OFF

ON

Execution

A >

B

 

ON

 

 

A

B

 

OFF

Operand

 

Name

 

 

Device

 

 

 

 

 

 

 

Register

 

 

 

 

 

 

Constant

Index

 

 

X

Y

R

S

T.

C.

XW

YW

RW

SW

T

C

D

 

I

 

J

K

 

 

A

Compared

 

 

 

 

 

 

 

 

 

 

data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

Reference

 

 

 

 

 

 

 

 

 

 

data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example

When R00C is ON, the data of D0125 is compared with the constant data 2500, and if the data of D0125 is greater than 2500, R020 is turned ON.

If the data of D0125 is 3000, the comparison result is true. Consequently, R020 is turned ON.

D0125

3000

>

Constant

2500

 

 

R020 is ON

 

If the data of D0125 is -100, the comparison result is false. Consequently, R020 is turned OFF.

D0125

-100

Constant

2500

R020 is OFF

Note

This instruction deals with the data as signed integer (-32768 to 32767).