8.2Variable input filter constant

Function

The input filter constant (ON/OFF delay time) of the leading 8 points X000 to X007 can be specified by user program within the range of 0 to 15ms. The default is 10ms. The setting value is recognized at the first scan. Therefore, it cannot be changed after the second scan.

Related registers

SW16 Function selection. Refer to section 8.1.

SW17 Input filter constant value

F E D C B A 9 8 7 6 5 4 3 2 1 0

No use (set to 0)

Setting value

0 to 15

Operation

Input signal

TTT T

Internal logic

Scan cycle

X device

T: Input filter constant (0 to 15ms)

Sample program

This program sets the input filter constant to 3ms.