8.2 Variable input filter constant

Function
The input filter constant (ON/OFF delay time) of the leading 8 points X000 to X007
can be specified by user program within the range of 0 to 15ms. The default is 10ms.
The setting value is recognized at the first scan. Therefore, it cannot be changed after
the second scan.
Related registers
SW16 Function selection. Refer to section 8.1.
SW17 Input filter constant value
FEDCBA9876543210
No use (set to 0)
Setting value
0 to 15
Operation
Input signal
Internal logic
Scan cycle
X device
T: Input filter constant (0 to 15ms)
Sample program
This program sets the input filter constant to 3ms.
TTTT