6F3B0253

7. Instructions

Transitional contact (Falling edge)

Expression

Input Output

Function

When the input at last scan is ON and the input at this scan is OFF, the output is turned ON. This instruction is used to detect the input changing from ON to OFF.

Execution condition

Input

Operation

Output

OFF

When the input state at last scan is OFF

OFF

 

When the input state at last scan is ON

ON

ON

Regardless of the input state at last scan

OFF

Operand

No operand is required.

Example

Coil Y022 comes ON for only 1 scan when the device X000 comes OFF.

X000

Y022

1 scan time1 scan time

Note

In case of T1, the maximum usable number in a program is 512. (

and

total)

In case of T1S, the maximum usable number in a program is 2048.

( P N (P) (N) total)

120 T1-16S User’s Manual